Toshiba MMC-AP0188HPUL Service Manual page 63

Table of Contents

Advertisement

Check code
Outdoor 7-segment display
Main
remote
Check
controller
Sub-code
code
Duplicated
indoor address
E08
E08
E09
Communication
error between
Application control
kit and indoor unit
E11
01:
Indoor-outdoor
communication
02:
Outdooroutdoor
communication
E12
E12
E15
E15
00:
Overloading
01-:
No. of units
connected
E16
E16
Location
Description
System status
of
detection
Indoor
Duplicated
All stop
unit
indoor address
I/F
Remote
Duplicated
Stop of
controller
master remote
corresponding
controller
unit
Indoor
Indoor-
Stop
unit
Application
control kit
communication
error
I/F
Automatic
All stop
address starting
error
I/F
Indoor unit not
All stop
found during
automatic
address setting
I/F
Too many
All stop
indoor units
connected
- 63 -
Error detection
Check items (locations)
condition(s)
More than one indoor unit is
Check indoor addresses.
assigned same address.
Check for any change
made to remote controller
connection (group /
individual) since indoor
address setting.
In two remote controller
Check remote controller
configuration (including
settings.
wireless), both controllers are
Check remote controller
set up as master. (Header
P.C. boards.
indoor unit is shut down with
alarm, while follower indoor
units continue operating.)
Displayed when error is
1. Check connector indoor
detected
unit (CN521(red))
Application control kit
(CN1 (red))
2. Check connection of
indoor-Applicat ion control
kit communication line.
3. Check indoor P.C. board.
4. Chec k Application control
kit P.C. board.
Indoor automatic address
Perform automatic address
setting is started while
setting again after
automatic address setting
disconnecting
for equipment in other
communication cable to
refrigerant line is in
that refrigerant line.
progress.
Outdoor automatic
address setting is started
while automatic address
setting for indoor units is in
progress.
Indoor unit cannot be
Check connection of
detected after indoor
indoor-outdoor
automatic address setting is
communication line.
started.
Check for error in indoor
power supply system.
Check for noise from other
devices.
Check for power failure.
Check for defect in indoor
P.C. board.
Combined capacity of
Check capacities of indoor
indoor units exceeds 135
units connected.
% of combined capacity of
Check combined HP
capacities of indoor units.
outdoor units.
Note:
Check HP capacity
settings of outdoor units.
If this code comes up
Check No. of indoor units
after backup setting for
outdoor unit failure is
connected.
performed, perform "No
Check for defect in outdoor
P.C. board (I/F).
overloading detected"
setting.
< "No overloading detected "
setting method>
Turn on SW09/Bit 2 on I/F
P.C. board of outdoor header
unit.
More than 48 indoor units
are connected.