Endress+Hauser Proline 200 PROFIBUS PA Brief Operating Instructions
Endress+Hauser Proline 200 PROFIBUS PA Brief Operating Instructions

Endress+Hauser Proline 200 PROFIBUS PA Brief Operating Instructions

Transmitter with coriolis sensor

Advertisement

Quick Links

KA01269D/06/EN/02.18
71409637
2018-08-01
Products
Brief Operating Instructions
Proline 200
PROFIBUS PA
Transmitter with Coriolis sensor
These instructions are Brief Operating Instructions; they are
not a substitute for the Operating Instructions pertaining to
the device.
Transmitter Brief Operating Instructions
Contain information about the transmitter.
Sensor Brief Operating Instructions →  3
Solutions
Services

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Proline 200 PROFIBUS PA and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Endress+Hauser Proline 200 PROFIBUS PA

  • Page 1 Products Solutions Services KA01269D/06/EN/02.18 71409637 2018-08-01 Brief Operating Instructions Proline 200 PROFIBUS PA Transmitter with Coriolis sensor These instructions are Brief Operating Instructions; they are not a substitute for the Operating Instructions pertaining to the device. Transmitter Brief Operating Instructions Contain information about the transmitter.
  • Page 2 Proline 200 PROFIBUS PA Order code: XXXXX-XXXXXX Ser. no.: XXXXXXXXXXXX Ext. ord. cd.: XXX.XXXX.XX Serial number www.endress.com/deviceviewer Endress+Hauser Operations App A0023555 Endress+Hauser...
  • Page 3 These Brief Operating Instructions are the Transmitter Brief Operating Instructions. The "Sensor Brief Operating Instructions" are available via: • Internet: www.endress.com/deviceviewer • Smart phone/tablet: Endress+Hauser Operations App Detailed information about the device can be found in the Operating Instructions and the other documentation: • Internet: www.endress.com/deviceviewer...
  • Page 4: Table Of Contents

    Table of contents Proline 200 PROFIBUS PA Table of contents Document information ............5 Symbols used .
  • Page 5: Document Information

    Proline 200 PROFIBUS PA Document information Document information Symbols used 1.1.1 Safety symbols Symbol Meaning DANGER! DANGER This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in serious or fatal injury. WARNING! This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in WARNING serious or fatal injury.
  • Page 6 Document information Proline 200 PROFIBUS PA Symbol Meaning Protective Earth (PE) A terminal which must be connected to ground prior to establishing any other connections. The ground terminals are situated inside and outside the device: • Inner ground terminal: Connects the protectiv earth to the mains supply.
  • Page 7: Basic Safety Instructions

    Proline 200 PROFIBUS PA Basic safety instructions Basic safety instructions Requirements for the personnel The personnel must fulfill the following requirements for its tasks: ‣ Trained, qualified specialists must have a relevant qualification for this specific function and task. ‣...
  • Page 8: Workplace Safety

    Verification for borderline cases: ‣ For special fluids and fluids for cleaning, Endress+Hauser is glad to provide assistance in verifying the corrosion resistance of fluid-wetted materials, but does not accept any warranty or liability as minute changes in the temperature, concentration or level of contamination in the process can alter the corrosion resistance properties.
  • Page 9: Product Safety

    It meets general safety standards and legal requirements. It also complies with the EU directives listed in the device-specific EU Declaration of Conformity. Endress+Hauser confirms this by affixing the CE mark to the device. IT security Our warranty is valid only if the device is installed and used as described in the Operating Instructions.
  • Page 10: Turning The Display Module

    Installation Proline 200 PROFIBUS PA max. 350° 8 mm 8 mm A0032242 Release the fixing screw. Turn the housing to the desired position. Firmly tighten the securing screw. Turning the display module The display module can be turned to optimize display readability and operability.
  • Page 11: Transmitter Post-Installation Check

    Proline 200 PROFIBUS PA Installation Transmitter post-installation check The post-installation check must always be performed after the following tasks: • Turning the transmitter housing • Turning the display module Is the device undamaged (visual inspection)?  Are the securing screw and securing clamp tightened securely? ...
  • Page 12: Electrical Connection

    Electrical connection Proline 200 PROFIBUS PA Electrical connection Connection conditions 5.1.1 Required tools • For cable entries: Use corresponding tools • For securing clamp: Allen key 3 mm • Wire stripper • When using stranded cables: Crimper for wire end ferrule •...
  • Page 13 Proline 200 PROFIBUS PA Electrical connection 5.1.3 Fieldbus cable specification Cable type In accordance with IEC 61158-2 (MBP), cable type A is recommended. Cable type A has a cable shielding that guarantees adequate protection from electromagnetic interference and thus the most reliable data transfer.
  • Page 14 Electrical connection Proline 200 PROFIBUS PA Maximum spur length The line between the distribution box and field device is described as a spur. In the case of applications in non-hazardous areas, the max. length of a spur depends on the number of spurs >1 m (3.28 ft):...
  • Page 15 Proline 200 PROFIBUS PA Electrical connection 5.1.4 Terminal assignment Transmitter Connection version for PROFIBUS PA, pulse/frequency/switch output A0013570 A0018161 Maximum number of terminals Maximum number of terminals for order code for "Accessory mounted", option NA "Overvoltage protection" Output 1: PROFIBUS PA...
  • Page 16 Electrical connection Proline 200 PROFIBUS PA For reasons concerning explosion protection, it is recommended that grounding be dispensed with. To comply with both requirements, there are basically three different types of shielding in the fieldbus system: • Shielding at both ends •...
  • Page 17 Proline 200 PROFIBUS PA Electrical connection A0028768  1 Connection example for PROFIBUS PA Control system (e.g. PLC) PROFIBUS PA segment coupler Cable shield: the cable shield must be grounded at both ends to comply with EMC requirements; observe cable specifications...
  • Page 18: Connecting The Measuring Device

    Electrical connection Proline 200 PROFIBUS PA 5.1.8 Preparing the measuring device NOTICE Insufficient sealing of the housing! Operational reliability of the measuring device could be compromised. ‣ Use suitable cable glands corresponding to the degree of protection. Remove dummy plug if present.
  • Page 19 Proline 200 PROFIBUS PA Electrical connection Connection via terminals 3 mm 20 mm 10 (0.4) mm (in) A0032239 Loosen the securing clamp of the connection compartment cover. Unscrew the connection compartment cover. Push the cable through the cable entry . To ensure tight sealing, do not remove the sealing ring from the cable entry.
  • Page 20 Electrical connection Proline 200 PROFIBUS PA Connection via device plug A0032229 ‣ Plug in the device plug and tighten firmly. Removing a cable 3 (0.12) A0032240 ‣ To remove a cable from the terminal, use a flat-blade screwdriver to push the slot between the two terminal holes while simultaneously pulling the cable end out of the terminal.
  • Page 21: Ensuring The Degree Of Protection

    Proline 200 PROFIBUS PA Electrical connection Ensuring the degree of protection The measuring device fulfills all the requirements for the IP66/67 degree of protection, Type 4X enclosure. To guarantee IP66/67 degree of protection, Type 4X enclosure, carry out the following steps after the electrical connection: Check that the housing seals are clean and fitted correctly.
  • Page 22: Operation Options

    Operation options Proline 200 PROFIBUS PA Operation options Overview of operation options A0032227 Local operation via display module Computer with operating tool (e.g. FieldCare, SIMATIC PDM) Control system (e.g. PLC) Endress+Hauser...
  • Page 23: Structure And Function Of The Operating Menu

    Proline 200 PROFIBUS PA Operation options Structure and function of the operating menu 6.2.1 Structure of the operating menu Operating menu for operators and maintenances Language Operation task-oriented Setup Diagnostics Operating menu for experts Expert function-oriented A0014058-EN  2 Schematic structure of the operating menu 6.2.2...
  • Page 24: Access To The Operating Menu Via The Local Display

    Operation options Proline 200 PROFIBUS PA Access to the operating menu via the local display X X X X X X 19.184 mA 12.5 X X X X X X Language 20.50 Ã English Deutsch Español Français Xxxxxxx A B C D E F G H I J K M N O P Q R S T U V W +0.000 Xx...
  • Page 25 Proline 200 PROFIBUS PA Operation options 6.3.1 Operational display Explanatory symbols for the measured value Status area • Depends on the device version, e.g.: The following symbols appear in the status area of the – : Volume flow operational display at the top right: –...
  • Page 26 Operation options Proline 200 PROFIBUS PA Numeric editor Confirms selection. Moves the input position one position to the left. Exits the input without applying the changes. Inserts decimal separator at the input position. Inserts minus sign at the input position.
  • Page 27: Access To The Operating Menu Via The Operating Tool

    Proline 200 PROFIBUS PA System integration Keys and meaning Reduces the contrast (brighter setting). Plus/Enter key combination (press and hold down the keys simultaneously) Increases the contrast (darker setting). Minus/Plus/Enter key combination (press the keys simultaneously) For operational display:Enables or disables the keypad lock.
  • Page 28: Commissioning

    Commissioning Proline 200 PROFIBUS PA Commissioning Function check Before commissioning the measuring device: ‣ Make sure that the post-installation and post-connection checks have been performed. • "Post-installation check" checklist→  11 • "Post-connection check" checklist →  21 Switching on the measuring device ‣...
  • Page 29: Configuring The Measuring Device

    Proline 200 PROFIBUS PA Commissioning X X X X X X X 20.50 Main menu 0104-1 Display language English Operation Setup Display language 0104-1 English à Deutsch Español Français Display language 0104-1 à English Deutsch Español Français Hauptmenü 0104-1 Sprache...
  • Page 30: Defining The Tag Name

    Commissioning Proline 200 PROFIBUS PA Wizard Meaning Low flow cut off Set the low flow cut off Partially filled pipe detection Configure partial and empty pipe detection Current input Configure the current input Defining the tag name To enable fast identification of the measuring point within the system, you can enter a unique designation using the Device tag parameter and thus change the factory setting.
  • Page 31: Diagnostic Information

    Proline 200 PROFIBUS PA Diagnostic information Diagnostic information Faults detected by the self-monitoring system of the measuring device are displayed as a diagnostic message in alternation with the operational display. The message about remedial measures can be called up from the diagnostic message, and contains important information on the fault.
  • Page 32 www.addresses.endress.com...