11.4.27 Calibration positions
The values of the factory calibration can be read out with the Calibration positions parameter.
The values are analog values of the potentiometer in the mechanical end positions of the actuator.
Index Sub-
Off-
Access
In-
set
Rights
dex
0x55
1
0
RO
2
16
RO
Description of parameter values
Index name
Calibration positions
11.4.28 Cycle counter
Switching cycles of the actuator or of the valve are counted with the Cycle counter parameter.
For a switching cycle, end position OPEN and then end position CLOSED must be detected. This also means that cycles are not
counted for a programming/initialization error.
Index Sub-
Off-
Access
In-
set
Rights
dex
0x56
1
0
R/W
2
32
RO
Description of parameter values
Index name
Cycle counter
11.4.29 Failure counter
For the Failure counter parameter, occurring errors and events are counted and emitted.
Index Sub-
Off-
Access
In-
set
Rights
dex
0x57
1
0
RO
2
16
RO
3
32
RO
4
48
RO
5
64
RO
6
80
RO
7
96
RO
8
112
RO
9
128
RO
www.gemu-group.com
Length
Index name
12 bits
Calibration
positions
12 bits
Parameter
Values
Max.
0 ... 4092
Min.
0 ... 4092
Length
Index name
24 bits
Cycle counter
24 bits
Parameter
Values
User
0 ... 16.777.215 Customer switching cycles (resettable)
Total
0 ... 16.777.215 Total of switching cycles (not resettable)
Length
Index name
16 bits
Failure counter
16 bits
16 bits
16 bits
16 bits
16 bits
16 bits
16 bits
16 bits
Parameter
Type
Max.
uint:16
Min.
uint:16
Read out analog value of the potentiometer for the mechan-
ical end position OPEN.
Read out analog value of the potentiometer for the mechan-
ical end position CLOSED.
Parameter
Type
User
uint:24
Total
uint:24
Parameter
Type
Undervoltage
uint: 16
Temperature error
uint: 16
Motor unable to
uint: 16
move
Internal error
uint: 16
Emergency power
uint: 16
Potifail open
uint: 16
Potifail close
uint: 16
Overcurrent out 1
uint: 16
Overcurrent out 2
uint: 16
37 / 52
11 Specific data IO-Link (pin 6)
Default
Values
0
0 ... 4092
4092
0 ... 4092
Description
Default
Values
0
0 ... 16.777.215
0
0 ... 16.777.215
Description
Default
Values
-
0 ... 65.535
-
0 ... 65.535
-
0 ... 65.535
-
0 ... 65.535
-
0 ... 65.535
-
0 ... 65.535
-
0 ... 65.535
-
0 ... 65.535
-
0 ... 65.535
GEMÜ Q50 eSyStep
Open / Close (Code AE, A5, A6)