rights
0x4F
0
R/W
0x50
1
R/W
2
R/W
3
R/W
4
R/W
0x51
1
R/W
2
R/W
3
RO
4
RO
0x53
1
RO
2
RO
3
RO
0x55
1
RO
2
RO
0x56
1
R/W
2
RO
0x57
1
RO
2
RO
3
RO
4
RO
www.gemu-group.com
Index name
Error action
Error action
Basic settings
Inversion of LED col-
On site initialization
Initialization mode
IO-Link process data Activate/deactivate
Actuator position
Open request
feedback
Close request
Initialized positions
Calibrated positions
Cycle counter
Failure counter
Undervoltage
Temperature error Number of errors or
Motor unable to
Internal error
Parameter
Function
Set safety position
Activate / deactiv-
ours
ate inversion of
LEDs
Activate / deactiv-
ate on site initializa-
tion
Set initialization
mode
auto / manual
use of IO-Link pro-
cess data
Request valve posi-
tion OPEN
Request valve posi-
tion CLOSED
Open real
Real valve position
OPEN
Close real
Real valve position
CLOSED
Open
Analog value valve
position OPEN
Close
Analogue value
valve position
CLOSED
Stroke
Read out the analog
value for stroke (dif-
ference between
OPEN and CLOSED).
Max.
OPEN end position
Min.
CLOSED end posi-
tion
User
Customer switching
cycles (resettable)
Total
Total of switching
cycles (not reset-
table)
Number of under-
voltage errors (U <
17.4)
switch-offs of the
actuator due to
overtemperature
Motor fault / motor
move
blocked
Internal error of the
actuator
23 / 52
11 Specific data IO-Link (pin 6)
Factory
Setting options
settings
2
0 → Hold
1 → Open
2 → Close
0
0 → Standard
1 → Inversed
0
0 → Enabled
1 → Disabled
0
0 → Automatic
1 → Manual
0
0 → Disabled
1 → Enabled
900
30 ... 970
(90.0%)
(3.0 ... 97.0%)
100
30 ... 970
(10.0%)
(3.0 ... 97.0%)
0 ... 4095
0 ... 4095
0 ... 4095
0 ... 4095
0 ... 4095
0 ... 4095
0 ... 4095
0
0 ... 16.777.215
0
0 ... 16.777.215
0
0 ... 65.535
0
0 ... 65.535
0
0 ... 65.535
0
0 ... 65.535
GEMÜ Q50 eSyStep