Floating Point macro

This application macro is for applications where speed reference needs to be
controlled through digital inputs (DI5 & DI6). By activating digital input 5, the speed
reference increases, by activating digital input 6, the speed reference decreases. If
both digital inputs are active or inactive, the reference does not change.
Note: When constant speed 1 is activated using digital input 3 (DI3), the reference
speed is the value of parameter 1202. The value remains as the reference speed
when digital input 3 is deactivated.
mA
9902
1103
1401
1601
3415
Application macros
X1
Signal cable shield (screen)
1
SCR
Not configured
2
AI1
Analog input circuit common
3
AGND
Reference voltage 10 VDC
4
10V
Not configured
5
AI2
6
AGND
Analog input circuit common
7
AO1
Output frequency: 0(4)...20 mA
mA
8
AO2
Output current: 0(4)...20 mA
9
AGND
Analog output circuit common
Auxiliary voltage output +24 VDC
10 24V
Auxiliary voltage output common
11 GND
Digital input common for all
12 DCOM
Start/Stop: Activate to start drive
13 DI1
Run permissive: Deactivate to stop drive (P 1601)
14 DI2
Constant (Preset) speed 1 (P 1202)
15 DI3
Safety interlock 1: Deactivate to stop drive (P 1608)
16 DI4
Reference up: Activate to increase reference
17 DI5
Reference down: Activate to decrease reference
18 DI6
19 RO1C
Relay output 1 (P 1401)
Default operation: Started =>19 connected to 21
20 RO1A
21 RO1B
22 RO2C
Relay output 2 (P 1402)
Default operation: Running =>22 connected to 24
23 RO2A
24 RO2B
25 RO3C
Relay output 3 (P 1403)
Default operation: Fault (-1) =>25 connected to 27
26 RO3A
27 RO3B
Parameters Changed Relative to HVAC Default
Parameter
10 (
APPLIC MACRO
FLOATING PNT
1
7 (
5
REF
SEL
DI
1
7 (
RELAY OUTPUT
STARTED
2 (
2)
RUN ENABLE
DI
3
0105 (
SIGNAL
PARAM
(Fault => 25 connected to 26)
Value
Parameter
)
3416
SIGNAL
, 6
)
3417
U
D
SIGNAL
)
3419
OUTPUT
3420
OUTPUT
)
3421
TORQUE
OUTPUT
A
550-UH User's Manual
J1
Jumper Settings
...
AI1: 0(4)
20 mA
...
AI2: 0(4)
20 mA
1
Value
3
-200.0%
MIN
3
200.0%
MAX
3
4 (%)
UNIT
3
-200.0%
MIN
3
200.0%
MAX
ON
1
2