Inverter rating

6.1
Inverter rating
Model FR-A846-[]
LD
0.75
Applicable
motor capacity
ND
0.4
(kW)

(initial setting)
LD
1.6
Rated
capacity
ND
1.1
(kVA)

(initial setting)
LD
2.1
Rated
ND
current (A)
1.5
(initial setting)
LD
120% 60 s, 150% 3 s (inverse-time characteristics) at ambient temperature of 40°C
Overload
current
ND
150% 60 s, 200% 3 s (inverse-time characteristics) at ambient temperature of 40°C
rating

(initial setting)
Rated voltage
Three-phase 380 to 500 V

Maximum
Regenerative
brake torque
10% torque/continuous
braking

Rated input
Three-phase 380 to 500 V 50 Hz/60 Hz
AC voltage/frequency
Permissible AC voltage
323 to 550 V 50 Hz/60 Hz
fluctuation
Permissible frequency
±5%
fluctuation
LD
2.1
Rated input
ND
current (A)

1.5
(initial setting)
Power
LD
1.6
supply
capacity
ND
1.1
(kVA)
(initial setting)

IEC 60529
Dust- and water-proof type (IP55)
Protective
structure
UL50
UL Type12
Cooling system
Self cooling + internal fan
DC reactor
Built-in
Approx. mass (kg)
15

The applicable motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi Electric 4-pole standard motor.

The rated output capacity indicated assumes that the output voltage is 440 V.

The % value of the overload current rating indicated is the ratio of the overload current to the inverter's rated output current. For repeated duty,
allow time for the inverter and motor to return to or below the temperatures under 100% load.

The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within the setting range.
However, the maximum point of the voltage waveform at the inverter output side is the power supply voltage multiplied by about

Value for the ND rating.

The rated input current indicates a value at a rated output voltage. The impedance at the power supply side (including those of the input reactor
and cables) affects the rated input current.

The power supply capacity is the value when at the rated output current. It varies by the impedance at the power supply side (including those of
the input reactor and cables).

For the power voltage exceeding 480 V, set Pr.977 Input voltage mode selection. (For the details, refer to the FR-A800 Instruction Manual
(Detailed).)

UL Type 12 Enclosure-Suitable for Installation in a Compartment Handling Conditioned Air (Plenum)
 For compliance with IP55, remove the protective bushes and install the recommended cable glands.
128
SPECIFICATIONS
00023
00038
00052
00083
00126
(0.4K)
(0.75K)
(1.5K)
(2.2K)
(3.7K)
1.5
2.2
3.7
5.5
7.5
0.75
1.5
2.2
3.7
5.5
2.7
3.7
5.8
8.8
12
1.9
3
4.6
6.9
9.1
3.5
4.8
7.6
11.5
16
2.5
4
6
9
12
3.5
4.8
7.6
11.5
16
2.5
4
6
9
12
2.7
3.7
5.8
9
12
1.9
3
4.6
6.9
9

15
15
15
16
17
00170
00250
00310
00380
00470
(5.5K)
(7.5K)
(11K)
(15K)
(18.5K)
11
15
18.5
22
7.5
11
15
18.5
18
22
27
33
13
18
24
29
23
29
35
43
17
23
31
38

23
29
35
43
17
23
31
38
18
22
27
33
13
18
24
29

Forced-air-cooling + internal fan
26
26
27
27
00620
00770
00930
01160
01800
(22K)
(30K)
(37K)
(45K)
(55K)
30
37
45
55
75
22
30
37
45
55
43
53
65
81
110
34
43
54
66
84
57
70
85
106
144
44
57
71
86
110
57
70
85
106
144
44
57
71
86
110
43
53
65
81
110
34
43
54
66
102
59
60
63
64
147
02160
02600
03250
03610
(75K)
(90K)
(110K)
(132K)
90
110
132
160
75
90
110
132
137
165
198
248
110
137
165
198
180
216
260
325
144
180
216
260
180
216
260
325
144
180
216
260
137
165
198
248
110
137
165
198
150
153
189
193
.