Mitsubishi Electric 800 Series Instruction Manual page 68

Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

2.11.5
Connection of the multifunction regeneration
converter (FR-XC)
Common bus regeneration mode with harmonic suppression disabled
(Pr.416 = "0")
When connecting the multifunction regeneration converter (FR-XC) to suppress power harmonics, perform wiring securely as
follows. Incorrect connection will damage the multifunction regeneration converter and the inverter.
Turn ON switch 1 (connection mode setting switch) in the function selection switch assembly (SW2). If the switch setting does
not match the actual wiring, the connection mode fault "E.T" occurs.
After making sure that the wiring is correct and secure, set "2 or 102" in Pr.30 Regenerative function selection. (Refer to the
Instruction Manual (Detailed) of the FR-A800 inverter.)
MCCB
MC
∗8
Fuse
R/L1
∗8
Fuse
S/L2
Power
supply
∗8
Fuse
T/L3
FR-XC
FR-XCL
∗4∗9
R2/L12
R2/L12
S2/L22
S2/L22
T2/L32
T2/L32
∗4∗5
R/L1
S/L2
RYB
RSO
∗7
T/L3
R1/L11
S1/L21
RES
SOF
LOH
SD
Connection of stand-alone option units
Junction terminal
P/+
Fuse
N/-
Fuse
SE
C
B
A
Junction terminal
Fuse
Fuse
Junction terminal
Fuse
Fuse
INSTALLATION AND WIRING
Inverter
U
∗1
R/L1
V
S/L2
IM
M
W
T/L3
R1/L11
S1/L21
∗2∗3
P/+
P1
N/-
∗6
X10(MRS)
RES
SD
Inverter
∗1
U
R/L1
V
S/L2
IM
M
W
T/L3
R1/L11
S1/L21
P/+
∗2∗3
P1
N/-
X10(MRS)
∗6
RES
SD
Inverter
∗1
U
R/L1
V
S/L2
IM
M
W
T/L3
R1/L11
S1/L21
∗2∗3
P/+
P1
N/-
X10(MRS)
∗6
RES
SD
67