Regin REGIO MIDI Manual
Hide thumbs Also See for REGIO MIDI:
Table of Contents

Advertisement

W E TAK E B U I L D I N G
AU TO M AT I O N PER SO N A L LY
MANUAL
RE G IO M ID I
© Copyright AB Regin, Sweden, 2017

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the REGIO MIDI and is the answer not in the manual?

Questions and answers

Summary of Contents for Regin REGIO MIDI

  • Page 1 W E TAK E B U I L D I N G AU TO M AT I O N PER SO N A L LY MANUAL RE G IO M ID I © Copyright AB Regin, Sweden, 2017...
  • Page 2 The software described in this document is supplied under license by Regin and may be used or copied only in accordance with the terms of the license. No part of this document may be reproduced or transmitted in any form, in any fashion, electronically or mechanically, without the express, written permission of Regin.
  • Page 3: Table Of Contents

    Model overview ........................ 8 Design ..........................9 CHAPTER 4 TECHNICAL DATA ..................10 DIMENSIONS ........................10 COMMUNICATION ......................10 Accessories for Regio Midi ..................... 11 CHAPTER 5 INSTALLATION PREPARATIONS ..............12 ................12 IFFERENT VERSIONS OF TERMINALS AND PINS ........................... 12 SING LABELS ........................
  • Page 4 ........................56 ROST PROTECTION ..................56 LOW ROOM TEMPERATURE ALARM ........................56 IGHTING CONTROL CHAPTER 13 INDICATIONS ....................57 CHAPTER 14 DISPLAY HANDLING ..................58 ........................ 58 ISPLAY INDICATIONS ........................59 ARAMETER MENU CHAPTER 15 MEMORY FUNCTION ON POWER FAILURE ........... 66 CHAPTER 16 MODBUS SIGNAL TYPES ................
  • Page 5: Chapter 1 About The Manual

    The document Regio in EXO Projects, containing information on how to use Regio in the EXO system, can be downloaded from Regin’s FTP server. It is intended for our system customers who need to share files with us, e.g. at technical support. Contact one of our sales engineers to get access to the FTP server.
  • Page 6: Chapter 2 Introduction To Regio

    The modular design with a separate bottom plate for wiring makes the whole Regio series easy to install and commission. The controllers are mounted directly on the wall or on a wall box. Chapter 2 Introduction to Regio Regio Midi manual...
  • Page 7: Regio Midi

    Heating/Cooling with VAV-control • Cooling • Cooling/Cooling • Heating/Cooling/VAV (only available in …3-models, except C3DFOC) • Heating/Heating or Cooling via change-over (only available in …F-models) • Change-over with VAV- function Application examples Regio Midi manual Chapter 2 Introduction to Regio...
  • Page 8: Chapter 3 Models

    ● ● ● ● ● RC-C3DFOC ● ● Models for RC-CTH three-point ● ● RC-CT control (…T- ● ● ● RC-CTO models) ● ● ● RC-CDTO Table 1. The Midi models and their functions Chapter 3 Models Regio Midi manual...
  • Page 9: Design

    Design RC-C3H, RC-CTH RC-C3, RC-CT RC-C3O, RC-CTO RC-CDTO, RC-C3DOC, RCC-C3DOCS RC-CF RC-CFO RC-CDFO, RC-C3DFOC Regio Midi manual Chapter 3 Models...
  • Page 10: Chapter 4 Technical Data

    Warm-up time .......... < 2 min. (operational), 10 min. (maximum accuracy) Measuring principle ..........NDIR (Non-Dispersive Infrared Technology) ..................... 0…5000 ppm Measuring range CO Accuracy ............400…5000 ppm ± 25 ppm ± 3 % of the reading Signal update ...................... Every 5 seconds Chapter 4 Technical data Regio Midi manual...
  • Page 11: Accessories For Regio Midi

    ........................ CO2RT Service adapter for Regio Midi ................... RC-TEST Connection plates ....................RC-CONN:10 The accessories are available from Regin. For more information, see the product sheets and instructions for each product, search via www.regincontrols.com. Regio Midi manual Chapter 4 Technical data...
  • Page 12: Chapter 5 Installation Preparations

    The address on the sticker has a different meaning depending on what communication protocol is used. Chapter 5 Installation preparations Regio Midi manual...
  • Page 13: Configuration

    (254:30). The computer and the Regio unit should now be in contact with each other. © 8. Start setting parameters and functions for the Regio. See the manual for Regio tool more information. Regio Midi manual Chapter 5 Installation preparations...
  • Page 14: Setting Of Dip Switches (Models Without Display)

    This means that the built-in safety functions will not be disregarded. The controllers have different indications which can be used for troubleshooting. See the section Indications. Chapter 5 Installation preparations Regio Midi manual...
  • Page 15: Chapter 6 Installation

    G (terminal 10) and G0 (terminal 11). On the communication loop the A- terminal (terminal 42) should only be connected to another A-terminal and the B-terminal (terminal 43) to another B-terminal. Otherwise, the communication will not work. Regio Midi manual Chapter 6 Installation...
  • Page 16 Figure 8. Examples of bottom plate with terminals For detailed information on connection of a communication cable to the Midi-controllers, see the manual Regio in EXO Projects. Chapter 6 Installation Regio Midi manual...
  • Page 17: Measurement And Testing During Installation

    Measurement and testing during installation In order to make measurements and test the inputs/outputs of a Regio room controller during installation, Regin’s RC-TEST service adapter may be used. Simply align the pins at the bottom of the RC-TEST with the terminals contained in the controller’s socket and then plug the Regio electronics cassette into the terminals at the top of...
  • Page 18: Wiring For Basic Models With 3 Universal Outputs (Rc-C3H, Rc-C3, Rc-C3O)

    0…10 V control signal terminal is connected to terminal 22, and its supply terminals to terminals 10 and 11. Make sure that the reference pole G0 is connected to the correct terminal on the actuator. alternatively Lighting control On/Off Chapter 6 Installation Regio Midi manual...
  • Page 19 32 and 40, +C. Closed contact corresponds to occupancy. alternatively Window contact (DI). A potential-free contact is connected between terminals 33 and 40, +C. Closed contact indicates closed window. See also the section Occupancy detector in the chapter Operating modes. Regio Midi manual Chapter 6 Installation...
  • Page 20 Choosing NC (FS) gives direct action on output UO1, i.e. increasing signal (longer pulses) on increasing control output. This setting is used when UO1 is connected to a thermal actuator of type Regin RTAM-24 (NC). In the event of a power cut the valve will close.
  • Page 21: Wiring For Model For Co Control (Rc-C3Doc)

    0…10 V control signal terminal is connected to terminal 22 and its supply terminals to terminals 10 and 11. Make sure that the reference pole G0 is connected to the correct terminal on the actuator. alternatively Lighting control On/Off. Regio Midi manual Chapter 6 Installation...
  • Page 22 Window contact (DI). A potential-free contact is connected between terminals 33 and 40, +C. Closed contact indicates closed window. alternatively Change-over. Regin’s condensation sensor, KG-A/1 (FS). The sensor is connected DI2/CI between terminals 33 and 41, AGnd. alternatively Window contact (DI). A potential-free contact is connected between terminals 33 and 40, +C.
  • Page 23: Wiring For Model With Built-In Co Sensor (Rcc-C3Docs)

    23 and 20. This can be configured either © through the display or through Regio tool . The output signal for UO1 can be set to NC (normally closed) or NO (normally open). Regio Midi manual Chapter 6 Installation...
  • Page 24 32 and 40, +C. Closed contact corresponds to occupancy. alternatively Window contact (DI). A potential-free contact is connected between terminals 33 and 40, +C. Closed contact indicates closed window. Regin’s condensation sensor, KG-A/1 (FS). The sensor is connected DI2/CI between terminals 33 and 41, AGnd. alternatively Window contact (DI).
  • Page 25: Wiring For Models For Co Control And Fan Control (Rc-C3Dfoc)

    23 and 20. This can be configured either through © the display or through Regio tool . The output signal for UO1 can be set to NC (normally closed) or NO (normally open). Regio Midi manual Chapter 6 Installation...
  • Page 26 Window contact (DI). A potential-free contact is connected between terminals 33 and 40, +C. Closed contact indicates closed window. alternatively Change-over. Regin’s condensation sensor, KG-A/1 (FS). The sensor is connected between DI2/CI terminals 33 and 41, AGnd. alternatively Window contact (DI). A potential-free contact is connected between terminals 33 and 40, +C.
  • Page 27: Wiring For Models For Fan Control (Rc-Cf, Rc-Cfo, Rc-Cdfo)

    0 V common for UO. Internally connected to terminal 11, G0. For forced ventilation. 24 V AC output, max 0.5 A. A 24 V AC actuator is connected between terminal 22 and terminal 20, GDO. Regio Midi manual Chapter 6 Installation...
  • Page 28 32 and 40, +C. Closed contact corresponds to occupancy. alternatively Window contact (DI). A potential-free contact is connected between terminals 32 and 40, +C. Closed contact indicates closed window. See also the section Occupancy detector in the chapter Operating modes. Chapter 6 Installation Regio Midi manual...
  • Page 29 Choosing NC (factory setting) gives direct action on output UO1, i.e. increasing signal (longer pulses) on increasing control output. This setting is used when UO1 is connected to a thermal actuator of type Regin RTAM-24 (NC). In the event of a power cut the valve will close.
  • Page 30: Wiring For Models For Three-Point Control (Rc-Cth, Rc-Ct, Rc-Cto, Rc-Cdto)

    The actuator’s terminal for closing signal is connected to terminal 23. No function. For an external room sensor or supply air temperature limitation sensor, PT1000. Measuring range 0...50°C. The sensor is connected between terminals 30 and 41, AGnd. See Table 1, SW7. Chapter 6 Installation Regio Midi manual...
  • Page 31 Choosing NC (factory setting) gives direct action on output UO1, i.e. increasing signal (longer pulses) on increasing control output. This setting is used when UO1 is connected to a thermal actuator of type Regin RTAM-24 (NC). In the event of a power cut the valve will close.
  • Page 32: Chapter 7 Control Modes

    0...48 % of the control signal. When the control signal reaches 52 %, UO2 starts to operate and will be 10 V when the control signal is 100 %. See the figure below: Chapter 7 Control modes Regio Midi manual...
  • Page 33 (full supply air volume), regardless of what the controller output signal is. For VAV control, several basic flows exist for supply air depending on the current running mode. Regio Midi manual Chapter 7 Control modes...
  • Page 34 Heating Cooling Temp (°C) heating cooling Control mode 6: Cooling In control mode Cooling, the unit is always a cooling controller and controls according to the basic cooling setpoint plus the setpoint adjustment. Chapter 7 Control modes Regio Midi manual...
  • Page 35 100 that the damper is entirely open. The function is activated by configuring the appropriate parameter to a value less than 100. The cooling limitation is present in control modes 4, 5 and 8. The heating limitation is present in control modes 5 and 8. Regio Midi manual Chapter 7 Control modes...
  • Page 36 Y2 will open 0…100 % when the controller output is 52…100 %. See the figure below: At forced ventilation, Y3 will open fully as before, and Y2 will control depending on temperature. However, Y2 will not give any output unless the controller output is above 52 %. Chapter 7 Control modes Regio Midi manual...
  • Page 37 UO2 is 0…100 % linear to the heating demand 0…48 % and UO1 0…100 % to the heating demand 52…100 %. When the heating demand is 48…52 % UO2 will always output 100 % and UO1 0 %. Regio Midi manual Chapter 7 Control modes...
  • Page 38: Additional Features

    The cascade factor consists of the supply air controller being faster than the room controller. The cascade factor in Regio Midi acts as a divisor which affects both the P-band and I-time. Example: If the cascade factor is 3 and the room controller has a P-band of 10°C and an I- time of 300 s, the supply air controller will receive a P-band of 3°C and an I-time of 100 s.
  • Page 39 The controller will remain in forced ventilation throughout the set Bypass time (FS=2h). Three different alternatives can be selected for setting the function forced ventilation: • Not active (FS) • Forced ventilation at 100% heating or cooling output • Forced ventilation at 100% cooling output Regio Midi manual Chapter 7 Control modes...
  • Page 40 In addition, the minimum limitation for the heating output functions in all control modes. Chapter 7 Control modes Regio Midi manual...
  • Page 41 10 V is set, and the flow is then calculated linearly between these two end points. To configure the flow calculation, Parameter 81 has the additional option 8, “Flow calculation”. The calculated flow value may be shown in the display by setting parameter 42 to option 9. Regio Midi manual Chapter 7 Control modes...
  • Page 42: Chapter 8 Operating Modes

    19°C and 27°C. The setpoints can also be adjusted ± 3°C via the setpoint knob or the display. For controllers with display the background lighting is lit (dimmed). STANDBY and the current room temperature (or setpoint depending on the configuration) are shown in the display. Chapter 8 Operating modes Regio Midi manual...
  • Page 43 In this case, each press of the occupancy button will change the timer as follows: Off  1h  2h  3h  4h  5h  Off. Control modes Depending on various settings and values, the controller will be set to different control modes using different setpoints: Regio Midi manual Chapter 8 Operating modes...
  • Page 44: Activation Of The Different Operating Modes

    Bypass mode, the controller will change to Shutdown. If the Occupancy button is pressed in Shutdown mode, the controller will switch to Bypass. After a configurable period of time in Bypass (FS=2 hours), the controller will return to the pre-set operating mode. Chapter 8 Operating modes Regio Midi manual...
  • Page 45 0 and 60 minutes (FS=0 min). In Bypass on presence, there is a switch-off timer, which means that if there is no occupancy indication during this time (FS=10 min), the controller will return to the pre-set operating mode. Regio Midi manual Chapter 8 Operating modes...
  • Page 46 Occupancy button, i. e. you can change its operating mode to Off/Unoccupied (Shutdown) or Bypass. Command ”Shutdown” Command Bypass Off/Unoccupied Bypass Central commands should be regarded as events and can be changed locally via the Occupancy button. Chapter 8 Operating modes Regio Midi manual...
  • Page 47: Chapter 9 Setpoint Calculation

    In operating modes Occupied and Bypass the unit controls according to the basic heating setpoint or the basic cooling setpoint. The setpoint can also be adjusted via the setpoint knob or display. The setpoint change takes place halfway between the setpoints with a hysteresis of 0.1°C. Regio Midi manual Chapter 9 Setpoint calculation...
  • Page 48 3 = The sum of the cooling setpoint and the adjustment is shown in the display. The adjustment is added to both the heating and cooling setpoints. Chapter 9 Setpoint calculation Regio Midi manual...
  • Page 49: Chapter 10 Actuators

    0 % or 100 %. This takes place via Modbus (Coil status register 23) or using © Regio tool On/Off actuators On/Off actuators can be used in control modes 0-8. Control mode: 0 = Heating 1 = Heating/Heating Regio Midi manual Chapter 10 Actuators...
  • Page 50 On units with a display, the exercise can be inactivated by setting parameters 36 and 37 to zero (0). Chapter 10 Actuators Regio Midi manual...
  • Page 51: Chapter 11 Fan Control

    If the temperature is not within the set temperature limits, the fan will be started in the corresponding Auto position, regardless of the settings. Regio Midi manual Chapter 11 Fan control...
  • Page 52 Heating, Heating/Heating, Heating or Cooling via change-over, Heating/Heating or Cooling via change-over, Heating/Cooling, Cooling/Cooling and Cooling. The function will add a minimum limit to UO3, so that the fan will have sufficient supply voltage. Chapter 11 Fan control Regio Midi manual...
  • Page 53 If the controller has a fan switch (only applies to models without a display), fan control will instead return to the current fan speed mode. Regio Midi manual Chapter 11 Fan control...
  • Page 54 Kickstart is activated when the lowest fan speed is selected. The function is also active during manual fan control. After the set time (1-10 s) has elapsed, the fan will return to its original speed. Chapter 11 Fan control Regio Midi manual...
  • Page 55: Chapter 12 Special Functions

    This setting may be changed using parameters number 9 and 10. Forced ventilation All Regio midi controllers have functionality for forced ventilation. All controllers except RC- C3DFOC have a digital output for controlling a forcing damper to increase the airflow to the room.
  • Page 56: Condensation Sensor

    Condensation sensor There is a special input (CI) on all Regio controllers. This input is intended for Regin’s Special input CI condensation sensor, KG-A/1, and functions internally as a digital input, i. e. condensation or no condensation. When the condensation sensor is activated, the cooling control is blocked and the controller is set in neutral position.
  • Page 57: Chapter 13 Indications

    On Regio models with a display, these indications are shown in the display. See the chapter Display handling. Communication LED When the frame has been removed, a LED is visible in the right edge of the controller. It lights up green when the controller is sending information. Regio Midi manual Chapter 13 Indications...
  • Page 58: Chapter 14 Display Handling

    COOL/HEAT: Shows if the unit controls according to the heating or cooling setpoint STANDBY: Standby indication SERVICE: Is shown when parameters are set, flashes when there is something wrong with the controller Figure 20. Indications in the display Chapter 14 Display handling Regio Midi manual...
  • Page 59: Parameter Menu

    Occupancy and INCREASE/DECREASE buttons active Only fan button active Occupancy and fan buttons active INCREASE/DECREASE and fan buttons active All buttons active Configuration Occupancy INCREASE/DECREASE Fan button options button active buttons active active Regio Midi manual Chapter 14 Display handling...
  • Page 60 State connected sensor on UI1: (All models except RC-C3DOC, RCC-C3DOCS, RC-C3DFOC ) 0=None 1=Change-over digital 2=Change-over analogue State connected sensor on DI1: 0=Not active 1=Window contact 2= No function 3= Presence detector 4=Change-over sensor (RC-C3DOC, RCC-C3DOCS, RC-C3DFOC ) 5-6=No function Chapter 14 Display handling Regio Midi manual...
  • Page 61 Time in hours between exercise of cooling actuators Hysteresis for on/off actuators and heating Hysteresis for on/off actuators and cooling Minimum limit for the heat output 20 % The fan will never stop 0=OFF 1=ON Regio Midi manual Chapter 14 Display handling...
  • Page 62 State NO/NC digital input 2: 0=NO (Normally open) 1=NC (Normally closed) State NO/NC universal input 1: 0=NO (Normally open) 1=NC (Normally closed) Manual/Auto Heating output: 0=Off 1=Manual 2=Auto Manual/Auto cooling output: 0=Off 1=Manual 2=Auto Chapter 14 Display handling Regio Midi manual...
  • Page 63 0 l/s Flow at 10 V input in AI2 100 l/s Minimum runtime when calculating for change over 600s Alarm limit for high room temperature 40°C Alarm limit for low room temperature 15°C Regio Midi manual Chapter 14 Display handling...
  • Page 64 BACnet MS/TP Max master. COMbus speed: 0=9600 1=19200 2=38400 3=76800 (only BACnet) COMbus reset. 0 (deactivated) When activated (1) it resets the communication to default settings Min limit for EC fan (%) 10 % Chapter 14 Display handling Regio Midi manual...
  • Page 65 1 = Advanced Use valve exercise 0 = Never 1 = Regularly 2 = Regularly and at power-up 3 = Regularly, at power-up and when changing state to Occupied Table 15. Parameter list Regio Midi manual Chapter 14 Display handling...
  • Page 66: Chapter 15 Memory Function On Power Failure

    Activation of Bypass is not stored in the memory. Instead, the controller will return to the pre- set operating mode after power failure. However, the set operating mode will be saved if central control is being used (parameter 47). Chapter 15 Memory function on power failure Regio Midi manual...
  • Page 67: Chapter 16 Modbus Signal Types

    A and B are used for both transmission and reception. Regio Midi manual Chapter 16 Modbus signal types...
  • Page 68 EXOline and Modbus will not function. If odd or even is chosen, only one stop-bit is used, or there will be too many bits altogether: 1 start-bit, 8 data-bits, 1 parity-bit and 1 stop-bit give a total of 11 bits which is the maximum amount. Chapter 16 Modbus signal types Regio Midi manual...
  • Page 69: Chapter 17 Modbus Signals

    Not used in this model RC_Actual_L.RegioDigOut3 Value of universal digital output 3 RC_Actual_L.RegioPresence Indicate presence RC_Actual_L.RegioRoomTempHighTempAlarm L,2 Indicate high room temperature alarm RC_Actual_L.RegioRoomTempLowTempAlarm Indicate low room temperature alarm RC_Actual_L.RegioDICO2 Indicate high CO level Regio Midi manual Chapter 17 Modbus signals...
  • Page 70: Coil Status Register

    0=Off 1=On RC_Setp_L.RegioCVCoolPulsPropNC L,1 Selection of cooling output functions (NO/NC): 0=NO (Normally open) 1=NC (Normally closed) Resets communication to default RC_Setp_L.RegioComFactoryDefault values: 1=Reset (returns to 0) RC_Setp_L.RegioBlockConfig Prevents parameter menu access via display Chapter 17 Modbus signals Regio Midi manual...
  • Page 71: Input Register

    0=Fan switched off 1=Fan speed 1 2=Fan speed 2 3=Fan speed 3 4=Auto RC_Actual_X.RegioUnitState X, 4 Indicate current unit state: 0=Off 1=Unoccupied 2=Stand-by 3=Occupied 4=Bypass RC_Actual_X.RegioControllerState X, 4 Indicate current controller state: 0=Off 1=Heating 2=Cooling Regio Midi manual Chapter 17 Modbus signals...
  • Page 72: Holding Register

    Holding register Signal name Type Modbus Default Scale Description address value factor RC_Setp_X.AlaModStat X, 3 Not used RC_SetP_X.RegioFreeCoolAvailable X, 3 Sequence order for Y2 and 0=Y2 activates before Y3 1=Y3 activates before Y2 Chapter 17 Modbus signals Regio Midi manual...
  • Page 73 0=Heat control 1=Cool control 2=Automatic change over depending on analogue sensor input or digital input RC_Setp_X.RegioRemoteState X, 3 Select operating mode for central control: 0=Off 1=Unoccupied 2=Stand-by 3=Occupied 5=No central control Regio Midi manual Chapter 17 Modbus signals...
  • Page 74 2=10…2 V 3=10…0 V RC_Setp_X.RegioCVHeatExerciseInter X, 3 Time in hours between exercise of heating actuators RC_Setp_X.RegioCVCoolExerciseInter X, 3 Time in hours between exercise of cooling actuators Not used in this model X, 3 Chapter 17 Modbus signals Regio Midi manual...
  • Page 75 Not used in this model X, 3 RC_Setp_X.RegioUi1 X, 3 State connected sensor on UI1: (All models except RC-C3DOC, RCC-C3DOCS, RC-C3DFOC) 0=None 1=Change-over digital 2=Change-over analogue Not used in this model X, 3 31-34 Regio Midi manual Chapter 17 Modbus signals...
  • Page 76 6=None RC_Setp_X.RegioUo2 (Not –T- X, 3 State connected function on models) UO2: 0=None 1=None 2=Thermal actuator Cool 3=None 4=Cooling actuator 0…10 V 5=None 6=On/off actuator cool RC_Setp_X.RegioModbusSlaveAddr X, 3 Factory Controller Modbus address Chapter 17 Modbus signals Regio Midi manual...
  • Page 77 -concentration in the room in ppm (RC-C3DOC, RCC-C3DOCS, RC-C3DFOC) 6=Heating setpoint +setpoint offset 7=Cooling setpoint+setpoint offset 8=Average of heating and cooling setpoint+setpoint offset 9=The calculated flow in the duct in l/s (RC-C3DOC, RCC-C3DOCS, RC-C3DFOC ) Regio Midi manual Chapter 17 Modbus signals...
  • Page 78 Disconnect timer with Occupancy/Unoccupancy RC_Setp_I.RegioPresenceOnTime I, 3 0 min Switch-on delay for Occupancy RC_Setp_I.RegioCVHeatPeriodTime I, 3 Period time for heating actuators with thermal actuator RC_Setp_I.RegioCVCoolPeriodTime I, 3 Period time for cooling actuators with thermal actuator Chapter 17 Modbus signals Regio Midi manual...
  • Page 79 0°C Temperature compensation on AI1 RC_Setp_R. RegioUi1Comp R, 3 0°C Temperature compensation on UI1 RC_Setp_R.RegioInternalTempComp R, 3 0°C Temperature compensation on internal room sensor RC_Setp_R.RegioTempFilterFactor R, 3 Filter factor for analogue temperature inputs Regio Midi manual Chapter 17 Modbus signals...
  • Page 80 800ppm - Activate presence if CO level is higher (RC-C3DOC, RCC-C3DOCS, RC-C3DFOC) RC_Setp_R.RegioCO2PresenceHyst R, 3 160ppm - Deactivate presence if the level is lower than the limit minus this hysteresis (RC-C3DOC, RCC-C3DOCS, RC-C3DFOC) Chapter 17 Modbus signals Regio Midi manual...
  • Page 81 Basic flow at “Off” when RCPSettings.RegioMinFlowOff R, 3 control state “Heating/Cooling with VAV- control” or “Heating/Cooling/VAV” is configured RC_Setp_R.SupplyAirTLim_HeatHi R, 3 Supply air max limitation for 35°C cascade control and heating control Regio Midi manual Chapter 17 Modbus signals...
  • Page 82 RC_Setp_X.RegioExerciseSelect X, 3 Use valve exercise 0 = Never 1 = Regularly 2 = Regularly and at power- 3 = Regularly, at power-up and when changing state to Occupied Chapter 17 Modbus signals Regio Midi manual...
  • Page 83: Chapter 18 Bacnet Signal Types

    Multistate inputs • Multistate values • Device Out_of_service The property out_of_service is not writable for all Object Types. Commandable The value objects are not commandable (i.e. does not use a priority array). Regio Midi manual Chapter 18 BACnet signal types...
  • Page 84: Chapter 19 Bacnet Signals

    Room base setpoint cooling Analog value, 9 °C RC_Setp_R.RegioUnOccSetPHeat Room heat setpoint in unoccupied mode Analog value, 10 °C RC_Setp_R.RegioUnOccSetPCool Room cool setpoint in unoccupied mode Analog value, 11 °C RC_Setp_R.RegioFrostSetP Frost protection setpoint Chapter 19 BACnet signals Regio Midi manual...
  • Page 85 Calculated supply air setpoint Analog value, 32-34 No function value when damper starts Analog value, 35 ppm Yes RC_SetpExt_R.RegioCO2LimitLow to open value when damper is Analog value, 36 ppm Yes RC_SetpExt_R.RegioCO2LimitHigh fully open Regio Midi manual Chapter 19 BACnet signals...
  • Page 86: Binary Inputs

    Binary ACTIVE/ RC_Setp_L.RegioBypass Force the unit in Bypass mode. value, 9 INACTIVE Is automatically returned after Bypass time (default=120 min) Binary ACTIVE/ RC_Setp _L.RegioShutDown Force the unit in ShutDown value, 10 INACTIVE state Chapter 19 BACnet signals Regio Midi manual...
  • Page 87: Loop

    4=Fan speed 3 Multistate values Object name Object-ID Description Values Writable Multistate 1=Off RC_Setp_X.RegioHeatOutputSelect Manual/Auto heat output value, 0 2=Manual output 3=Automatic output RC_Setp_X.RegioCoolOutputSelect Multistate 1=Off Manual/Auto cool output value, 1 2=Manual output 3=Automatic output Regio Midi manual Chapter 19 BACnet signals...
  • Page 88: Device

    EASE and fan button 8=All buttons Device The device object contains two writable properties; Description and Location. Description can be 17 characters long, and Location can be 33 characters long, if using single byte character encoding. Chapter 19 BACnet signals Regio Midi manual...
  • Page 89 Display indications 58 Display indications 58 About the manual 5 Index More information 5 Terms 5 Exercise 50 Activation of the different operating modes 44 Actuators 49 Analogue actuators 49 Exercise 50 Fan control 51 On/Off actuators 49 Auto control 51 Thermal actuators 49 Fan stopped 51 Three-point actuators 49...
  • Page 90 Multistate values 86 Basic setpoint 47 Calculation of the active setpoint 47 Setpoint displacement 47 Setpoint displacement 47 Special functions 55 Occupancy button 46, 57 Special input CI 55 Occupancy detector 45, 46 Split output signal 35 Occupied 43 Stand-by 42, 47 Occupied/Bypass 47 SW1-7 14 Off 42, 47...

Table of Contents