Siemens SIMATIC NET RUGGEDCOM RS950G Installation Manual page 38

Rugged ethernet switches
Hide thumbs Also See for SIMATIC NET RUGGEDCOM RS950G:
Table of Contents

Advertisement

IEC 61000-4-29
IEC 61000-4-11
IEC 61000-4-12
IEC 61000-4-16
IEC 61000-4-17
IEC 60255-27
a
Siemens-specified severity levels
IEEE 1613 EMC Immunity Type Tests
Note
The RUGGEDCOM RS950G meets Class 2 requirements for an all-fiber configuration
and Class 1 requirements for copper ports.
RUGGEDCOM RS950G
Installation Manual, 01/2021, C79000-G8976-1037-06
Test
Description
Voltage Dips
and Interrupts
Damped
Oscillatory
Mains
Frequency
Voltage
Ripple on DC
Power Supply
Dielectric
Strength
HV Impulse
Description
ESD
Enclosure Contact
Radiated RFI
Enclosure Ports
Fast Transient
DC Line-to-Line
AC Line-to-Line
Earth Ground Ports
Oscillatory
DC Line-to-Line
AC Line-to-Line
HV Impulse
DC Line-to-Line
6.2 EMC and Environmental Type Tests
DC Line-to-Line
AC Line-to-Line
Signal Ports
differential mode @ 1 MHz
DC Line-to-Line
differential mode @ 1 MHz
AC Line-to-Line
differential mode @ 1 MHz
Signal Ports
30 V Continuous, 300 V for 1 s
DC Line-to-Line
30 V Continuous, 300 V for 1 s
DC Line-to-Line
Signal Ports
2 kV (Fail-Safe Relay output)
DC Line-to-Line
AC Line-to-Line
Signal Ports
5 kV (Fail-Safe Relay output)
DC Line-to-Line
AC Line-to-Line
Enclosure Air
Signal Ports
Signal Ports
2.5kV common, 1 kV differential mode @ 1 MHz
2.5 kV common, 1 kV differential mode @ 1 MHz
Signal Ports
Test Levels
30% for 0.1 s, 60% for
0.1 s, 100% for 0.05 s
30% for 1 period,
60% for 50 periods
100% for 5 periods,
100% for 50 periods
2.5 kV common, 1 kV
2.5 kV common, 1 kV
2.5 kV common, 1 kV
15%
1.5 kV
2 kV
5 kV
5 kV
Test Levels
± 2 kV, ± 4 kV, ± 8 kV
± 4 kV, ± 8 kV, ± 15 kV
35 V/m
± 4 kV @ 2.5 kHz
± 4 kV
± 4 kV
± 4 kV
2.5 kV common mode @ 1 MHz
5 kV (Failsafe Relay)
5 kV
Certification
Severity
Levels
 
 
 
3
3
3
4
4
3
 
 
 
 
 
 
29

Advertisement

Table of Contents