The Modbus Display & Control (MDC) is a device with two RS485 ports, a keypad for setting parameters and a display to view the status of the connected equipment. The RS485 master port communicates with ebm-papst Modbus enabled, Electronically Commutated (EC) fans with software version 5.0 or later using a two-wire plus ground RS485 connection.
Operating and Maintenance Instructions Overview 3.1 Specification Product Modbus Display & Control - CN1116 Supply Voltage Two sets of connections are provided for either: (Reverse Polarity Protected) • 9 VDC to 57VDC from an optional external PSU or • 10 VDC sourced from connection to at least two EC fans 10V reference outputs* in parallel.
Modbus Master device. This operating mode allows exclusive access to all Modbus registers on each fan according to the latest ebm-papst parameter specification for Modbus enabled motors. A copy of this parameter specification is available on request by e-mail at info@uk.ebmpapst.com.
Figure 18 – Sensor-Fan wiring diagram with power supply We recommend using ebm-papst SN1120 or SN1121 series differential pressure sensors as they have been specifically designed for fan arrays and can be powered from a fan’s 10V 10mA, or 24V supply. It simplifies the...
Operating and Maintenance Instructions 12.0 WEEE (Waste Electrical and Electronic Equipment) ebm-papst UK Ltd complies with the Waste Electrical and Electronic Equipment (WEEE) Regulations through membership of a producer compliance scheme (PCS) as a B2B producer. EEE Producer registration number: WEE/CA0209WR 13.0 End of life...