Test
IEC 61000-4-16
IEC 61000-4-17
IEC 61000-4-18
IEC 61000-4-29
IEC 60255-5
EMC Immunity Type Tests per IEEE 1613
NOTE
The RUGGEDCOM RSG2100PF meets Class 2 requirements for an all-fiber configuration and Class 1
requirements for copper ports. Class 1 allows for temporary communication loss, while Class 2 requires
error-free and interrupted communications.
ESD
Radiated RFI
Fast Transient
Oscillatory
EMC and Environmental Type Tests
Description
Mains Frequency Voltage
Ripple on DC
Power Supply
Damped Oscillatory Wave
Voltage Dips
and Interrupts
Dielectric Strength
HV Impulse
Description
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal Ports
DC Power Ports
AC Power Ports
Earth Ground Ports
Signal Ports
DC Power Ports
Signal Ports
AC and DC Power Ports
DC Power Ports
Slow Damped
2.5 kV Common Mode
DC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Test Levels
30 V Continuous
300 V for 1s
10%
on Power and Signal
1.0 kV Differential
Mode on Power
30% for 0.1 s
60% for 0.1 s
100% for 0.05 s
2 kV (Fail-Safe
Relay Output)
2 kV
2 kV
5 kV (Fail-Safe
Relay Output)
5 kV
Test Levels
±2 kV
±4 kV
±8 kV
±4 kV
±8 kV
±15 kV
35 V/m
4 kV @ 2.5 kHz
4 kV
4 kV
4 kV
2.5 kV Common Mode @ 1 MHz
2.5 kV Common
Chapter 6
Certification
Severity Levels
4
3
3
41