Eaton Cutler-Hammer Digitrip 3000 Instructions For Installation, Operation And Maintenance page 46

Protective relay
Table of Contents

Advertisement

Page 40
Symptom
Circuit Breaker Trips
Much Slower than
Expected on Inverse
Time Overcurrent
Protective Relay
Indicates a Trip, but
Circuit Breaker Doesn't
Open
Auto-Reset Function not
Operational
Manual Reset Function
not Operational
Caution: When the Digitrip 3000 Protective Relay is Powered, it Supplies Voltage to the "b" Contacts
TABLE 6.1 TROUBLESHOOTING GUIDE (CONTINUED)
Probable Cause
The Short Delay Time
Setting Determines the
Minimum Inverse Time
Overcurrent
Improper Wiring from
Protective Relay
Unit in Test Mode with "No Trip
Test Selected"
Breaker "b" Contact to
Protective Relay not
Functioning
DIP Switch S9 not set correctly
Dip Switch S9 not set correctly
Damaged Reset Pushbutton
Possible Solution(s)
Check Coordination Curves for Short
Delay and Inverse Time Overcurrent
Settings
Check Trip Relay Wiring
NOTE: Instantaneous and Override
Trip Functions Close the
Contact Between TB2- 12 and
TB2-13, while Inverse Time
Overcurrent and External Trip
Functions Close the Contact
Between TB2-14 and TB2-15
Check that Trip Contact on Protective
Relay makes
Select Trip Test while in the Test Mode
Check Wiring from Protective Relay to
Circuit Breaker Trip Coil
Check that Circuit Breaker has Source
of Tripping Power
Check wiring from Breaker "b" Dry
Contact to TB1-9 and TB1 -10 of
Protective Relay Terminal Block
Check DIP Switch S9 Setting
Check that "b" Contact is Operational
Check DIP Switch Setting
Replace Protective Relay
I.B. 17555C
Reference
Section 7,
Paragraph 3-3.1
Figure 3-1
Figure 3-1
Paragraph 3-3.3
Wiring Plan Drawing
Wiring Plan Drawing
Figure 3-1 and 5-3
Table 5.1
Figure 5-3
Table 5.1
Paragraph 6-3
Effective November 1999