Follow these recommendations for copper data cabling in high electrical noise
environments:
1.5.3

Supported Fiber Optic Cables

The following fiber optic cable types are supported under the stated conditions.
Cable Type
Wavelength (nm) Modal Bandwidth
OM1 (62.5/125)
OM2 (50/125)
a
OM3 (50/125)
a
OM4 (50/125)
a
Laser optimized.
RUGGEDCOM RSG2200
Installation Manual, 04/2021, C79000-G8976-1043-17
Data cable lengths should be as short as possible, preferably 3 m (10
ft) in length. Copper data cables should not be used for inter-building
communications.
Power and data cables should not be run in parallel for long distances, and
should be installed in separate conduits. Power and data cables should intersect
at 90° angles when necessary to reduce inductive coupling.
Shielded/screened cabling can be used when required. Care should be taken to
avoid the creation of ground loops with shielded cabling.
(MHz·km)
850
200
1300
500
850
500
1300
500
850
1500
1300
500
850
3500
1300
500
1.5.3 Supported Fiber Optic Cables
Distance (m)
100Base-FX
1000Base-SX
275
2000
550
2000
550
2000
550
2000
Introduction
10GBase-SR
33
82
300
400
5