To connect an external power supply for the PoE ports, do the following:
Electrical hazard – risk of damage to equipment
Only connect the external PoE power supply to the terminals 5 and 7.
1.
2.
3.
4.
RUGGEDCOM RSG2300PF
Installation Manual, 04/2021, C79000-G8976-1348-09
NOTICE
Remove the terminal block cover.
If a screw-type terminal block is installed, remove the screws from terminals
5 and 7. Use these screws along with #6 ring lugs to secure the wires to the
terminal block.
Connect the positive wire from the power source to terminal 5 (+/L) on the
terminal block.
1
3
3
3
Screw-Type Terminal Block
1
Pluggable Terminal Block
2
Jumper
3
Terminal 4 (Chassis Ground)
4
Terminal 5 (+/L)
5
Terminal 7 (-/N)
6
Chassis Ground Terminal
7
Figure 2.7
Terminal Block Wiring
Connect the negative wire from the power source to terminal 7 (-/N) on the
terminal block.
4
Installing the Device
2.5.2 Connecting External PoE Power