Bosch Rexroth AG

Interfaces

9 Interfaces

9.1 General information

NOTICE
Ensure that the functional earth is connected, as otherwise the electronics can
be destroyed by a potential difference between the operator display and the
control cabinet PC if the voltage supply is interrupted to only one device and es-
tablished again. A direct connection of the functional earth between operator
display and control cabinet PC is optimal. If the functional earth is connected to
a neutral point, the control cabinet PC and the operator display have to be con-
nected to this neutral point.
To avoid malfunctions, use only shielded cables and metallic or con-
ductive connector/coupling housings with large-area shield support.

9.2 Overview

The following connections are available at the control cabinet PC:
Labeling at the
Connection type
housing
X10
PC voltage supply:
DC 24 V
XDVI
DVI monitor or analog monitor
(via adapter)
XSER
CDI interface, data
XVID
CDI interface, image
XETH1, XETH2
Ethernet interfaces
10/100/1000 Base-T
XUSB1 to XUSB6 USB interfaces
Internal connections for extension cards
1, 2 slots or 4 slots (see
ble slots per PC box type" on
page
14/57
Material damages to electronics due to missing
functional earth!
"Availa-
19)
Connector type
Mating connector or cable
(at the device)
(from outside)
Male connector ter-
Socket terminal
minal PC4/3-G7.62
PC4/3-G7.62
DVI(A) socket
DVI connector
(24-pin and 5-pin)
RJ45 socket, 8-pin RJ45 plug
(Twisted pair, 8-wire)
RJ45 socket, 8-pin RJ45 plug
(Twisted pair, 8-wire)
RJ45 socket, 8-pin RJ45 plug
(Twisted pair, 8-wire)
USB socket, 4-pin,
USB plug, 4-pin
type A
PCI/PCIe
PCI/PCIe card
DOK-SUPPL*-VPB*40.3***-IT05-EN-P