7.9
Operation sequence of the burner
7.9.1
Burner start-up program
Standard
Remote control
Motor
Transformer
F-R-S valves
Flame
Lockout
5
s
4 5
7.10
Final checks
Block the flame sensor and turn off the remote controls:
the burner must start and then stop in lockout after
approximately 5 s after start-up.
Free the flame sensor and turn off the remote controls:
the burner must stop in lockout.
Block the flame sensor when the burner is operating:
the flame must turn off and the burner stop in lockout within
3 s.
Turn on the remote control TL followed by TS while the
burner is operating: the burner must stop.
Make sure that the mechanical locking systems
on the adjustment devices are fully tightened.
ATTENTION
20170350
Start-up, calibration and operation of the burner
s
3 7
s
3 8
s
5
s
2 . 5
s
Lock-out because of no ignition
5
s
4 5
s
3 7
s
30
GB
3 8
s
5
s
2 . 5
s
20171919
Fig. 30