M4M 20 NETWORK ANALYZER USER MANUAL
Please follow the instructions on EPiC Mobile to complete the pairing. Once the pairing is completed, a
confirmation pop-up will appear on the device as per below picture:
MODBUS RTU (M4M 20 Modbus, M4M 20 I/O, M4M 20 Rogowski, M4M 20-M Modbus product
versions)
This section is available on all the M4M 20 product versions with Modbus RTU embedded communication.
→ Communication → Modbus RTU
Menu
Description
Address
From 1 to 247.
Baud rate
9600, 19200, 38400, 57600, 115200.
Parity
Even, Odd, None.
See Modbus communication manual for details on Modbus communication protocol and communication map.
MODBUS TCP/IP (M4M 20 Ethernet, M4M 20-M Ethernet product versions)
This section is available on all the M4M 20 product versions with Modbus RTU embedded communication.
→ Communication → Modbus TCP/IP
Menu
Description
DHCP
Enable / Disable (disabled by default).
IP address
192.168.1.12 (by default).
Subnet mask
255.255.255.0 (by default).
Gateway
192.168.1.1 (by default).
TCP port
502 (by default).
If DHCP is disabled, the values of above configurations (IP address, subnet mask, gateway, TCP port) are
the default ones. In this case, it is possible to modify each of above configurations.
If DHCP is enabled, it is not needed to enter the above configurations as they are automatically set.
See Modbus communication manual for details on Modbus communication protocol and communication map.
Alarms
Passkey
Enter the underneath passkey
into EPIC to pair the device