FireClass FC503 User Manual page 55

Addressable fire control panels
Hide thumbs Also See for FC503:
Table of Contents

Advertisement

Note: The panel on board Open Collector
outputs (OC1, OC2) may not be programmed to
act as SC1.
Panel Alarm Trigger
When the PANEL ALARM TRIGGER? option is set
to YES, the relevant output becomes active on the
panel alarm condition. Alternatively, a more specific
trigger condition may be defined for the output. The
default setting is YES.
Disablement Trigger
The DISABLEMENT TRIGGER? option activates the
relevant output if any system part is disabled. The
default setting is NO.
Note: This parameter is made available only
if the parameter PANEL ALARM TRIGGER for
the same output is set to NO. Setting the
parameter to YES will end the programming
sequence for that output. Outputs which have
this option programmed are not silenceable.
This feature is also available for Panel FIRE relay
and FC410RIM, FC410SIO, FC410MIO, FC410QMO,
FC410QRM, FC410QIO loop modules.
OUTPUT NAME
TRIGGER ZONE 1
TRIGGER ZONE 2
TRIGGER EVENT
SILENCEABLE
MONOSTABLE
Figure 30: Programming SC active on
disablements
Callout
1
2
3
4
5
6
7
8
FC503 and FC506 Addressable Fire Control Panels
Johnson Controls - CONFIDENTIAL
Description
Control panel name
Output number
Access level
Control panel status
If blinking, the control panel is
working properly
Output type
Output number
Insert output label
55