FireClass Precept EN13 Installation & Commissioning Manual

FireClass Precept EN13 Installation & Commissioning Manual

Fire detection/alarm panel & precept en repeater

Advertisement

Quick Links

EQUIPMENT:
PUBLICATION:
ISSUE No. & DATE:
Installation & Commissioning Manual
FIRECLASS PRECEPT EN13
FIRECLASS PREC EN13 INST
2
22/07/2021
Precept EN13 Fire Detection/Alarm Panel
& Precept EN Repeater
PAGE 1 of 32

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Precept EN13 and is the answer not in the manual?

Questions and answers

Summary of Contents for FireClass Precept EN13

  • Page 1 FIRECLASS PRECEPT EN13 EQUIPMENT: FIRECLASS PREC EN13 INST PUBLICATION: ISSUE No. & DATE: 22/07/2021 Precept EN13 Fire Detection/Alarm Panel & Precept EN Repeater Installation & Commissioning Manual PAGE 1 of 32...
  • Page 2: Table Of Contents

    FIRECLASS PRECEPT EN13 EQUIPMENT: FIRECLASS PREC EN13 INST PUBLICATION: ISSUE No. & DATE: 22/07/2021 List of Contents ..........2 15.1.2 T ’ IST OF IGURES O ACCESS THE NGINEER LOCK ..... 24 ..........2 ODULE UNCTIONS IST OF ABLES 15.2 C ....
  • Page 3: Introduction

    3. Introduction 4. Installation and Commissioning Overview The FIRECLASS Precept EN13 range of panels have been designed, manufactured and tested to This section lists the steps that are taken in meet the requirements of BSEN 54 Parts 2, 4 & 13...
  • Page 4: Igure 1 - Precept En13 2/4 Zigure 2 - Precept En13 8/16 Z

    FIRECLASS PREC EN13 INST PUBLICATION: ISSUE No. & DATE: 22/07/2021 5. Internal Panel Views Figure 1 – Precept EN13 2/4 Zone Internal View Secondary eart h bar E nclosure f ixing R em ovable C hassis f or cable screens...
  • Page 5: Igure Zone Precept En13 General Assembly Module )

    FIRECLASS PRECEPT EN13 EQUIPMENT: FIRECLASS PREC EN13 INST PUBLICATION: ISSUE No. & DATE: 22/07/2021 Figure 3 – 2/4 Zone Precept EN13 panel - General Assembly (with optional clock module) PAGE 5 of 32...
  • Page 6: 8/16 Zone Precept General Assembly ( Module )

    FIRECLASS PRECEPT EN13 EQUIPMENT: FIRECLASS PREC EN13 INST PUBLICATION: ISSUE No. & DATE: 22/07/2021 Figure 4 – 8/16 Zone Precept EN13 panel - General Assembly (with optional clock module) PAGE 6 of 32...
  • Page 7: One

    FIRECLASS PRECEPT EN13 EQUIPMENT: FIRECLASS PREC EN13 INST PUBLICATION: ISSUE No. & DATE: 22/07/2021 6. Typical wiring schematic – 16 Zone Figure 5 – Typical Wiring Diagram PAGE 7 of 32...
  • Page 8: Circuit

    FIRECLASS PRECEPT EN13 EQUIPMENT: FIRECLASS PREC EN13 INST PUBLICATION: ISSUE No. & DATE: 22/07/2021 Figure 6 – Typical Alarm Circuit Connection Diagram Typical Alarm Circuit Wiring Sounder Circuits are wired as a loop Each Alarm circuit from the panel motherboard is connected to the IN terminals on the Alarm Relay Board.
  • Page 9: Etails

    FIRECLASS PRECEPT EN13 EQUIPMENT: FIRECLASS PREC EN13 INST PUBLICATION: ISSUE No. & DATE: 22/07/2021 7. Circuit Connection Details 7.1 Motherboard Termination Details Figure 7 – C1627 Field Termination Inputs: Outputs: SIL = Silence alarms DIS = Disablement active EVAC = Evacuate...
  • Page 10: C1627 Motherboard

    FIRECLASS PRECEPT EN13 EQUIPMENT: FIRECLASS PREC EN13 INST PUBLICATION: ISSUE No. & DATE: 22/07/2021 8. C1627 Motherboard Features Figure 8 illustrates the motherboard features referred to elsewhere in the documentation. Figure 8 – C1627 Motherboard Layout Remote Inputs: Aux Outputs:...
  • Page 11: Power Supplies

    FIRECLASS PRECEPT EN13 EQUIPMENT: FIRECLASS PREC EN13 INST PUBLICATION: ISSUE No. & DATE: 22/07/2021 9. Power Supplies 2) A yellow ‘Batt/Charge Fault’ LED denoting any one of the following conditions: All panels produce dc power regulation directly on a) Battery or associated wiring disconnected the motherboard.
  • Page 12: Installation

    FIRECLASS PRECEPT EN13 EQUIPMENT: FIRECLASS PREC EN13 INST PUBLICATION: ISSUE No. & DATE: 22/07/2021 Installation danger to you and to anything else it touches. In case of accidental skin or eye contact, flush the The control panel must be installed by suitably...
  • Page 13: Installation Instructions

    FIRECLASS PRECEPT EN13 EQUIPMENT: FIRECLASS PREC EN13 INST PUBLICATION: ISSUE No. & DATE: 22/07/2021 10.2 Installation Instructions NOTE: The door and chassis both contain PCBs with sensitive and fragile electronic 1. Carefully remove the control panel from the components on them. You must place them packing and lay the panel on a flat surface.
  • Page 14: Optional C1631 R

    FIRECLASS PRECEPT EN13 EQUIPMENT: FIRECLASS PREC EN13 INST PUBLICATION: ISSUE No. & DATE: 22/07/2021 are trapped between the chassis and backbox. and the negative (black) terminal of the right- Do not connect the field wiring at this stage. hand battery. Note that the batteries will not power the panel until the mains supply is 22.
  • Page 15: Commissioning Checklist

    FIRECLASS PRECEPT EN13 EQUIPMENT: FIRECLASS PREC EN13 INST PUBLICATION: ISSUE No. & DATE: 22/07/2021 11.2 Commissioning Checklist 2. Detection zones should be commissioned next. The purpose is to establish the correct 1. Before commissioning, the engineer should functioning of each device and checking for check the following: correct indication at the control panel.
  • Page 16: Commissioningp

    11.6.1 Basic Default Configuration value of 3k9 must be used, which comply with the requirements laid down in the When first powered up, the Precept EN13 can be installation data sheets provided with the I.S. operated in the standard default mode without any barrier and the I.S.
  • Page 17: Zones

    FIRECLASS PRECEPT EN13 EQUIPMENT: FIRECLASS PREC EN13 INST PUBLICATION: ISSUE No. & DATE: 22/07/2021 11.7.2 Zones • The fire alarm devices operate correctly in line with the panel configuration. NOTE: panel determines normal • The Fire Routing and Fire protection outputs...
  • Page 18: Fire And Faultr

    FIRECLASS PRECEPT EN13 EQUIPMENT: FIRECLASS PREC EN13 INST PUBLICATION: ISSUE No. & DATE: 22/07/2021 11.7.4 Fire and Fault Routing Outputs remote equipment. The response should be verified for each signal. 1. Remove the resistor from the Fire Routing output circuit terminals and connect the field 11.7.7 Ancillary outputs...
  • Page 19: User Indications

    FIRECLASS PRECEPT EN13 EQUIPMENT: FIRECLASS PREC EN13 INST PUBLICATION: ISSUE No. & DATE: 22/07/2021 User Indications General Indicator Section Description Colour Operating Condition Power Supply On Green Illuminates Steady for Mains or Standby power On. Flashes on any new fire alarm condition, changing to a steady Fire indication on operation of Silence Alarms.
  • Page 20: User Controls

    FIRECLASS PRECEPT EN13 EQUIPMENT: FIRECLASS PREC EN13 INST PUBLICATION: ISSUE No. & DATE: 22/07/2021 User Controls POWER SUPPLY ON EVACUATE TEST DISPLAY FIRE FIRE ROUTING ACTIVE SILENCE/ GENERAL FAULT RESOUND ENABLE ALARMS POWER SUPPLY FAULT SYSTEM FAULT RESET DISABLE EARTH FAULT...
  • Page 21: Operating The Engineer

    Configure outputs to be delayed. zone or output: Note: The DIL switch labelled Configure M/S Zones With the cursor flashing on the selected zone or is not used on the Precept EN13 panels. output:  Pressing the ENABLE button will apply the 14.2...
  • Page 22: E Time - Out

    FIRECLASS PRECEPT EN13 EQUIPMENT: FIRECLASS PREC EN13 INST PUBLICATION: ISSUE No. & DATE: 22/07/2021 14.3 To Restore the Factory Default • Invalid condition: Selecting any config mode Configuration for Zones & Outputs: switch [SW1-4 to SW1-8] to the ON position whilst the panel is in the fire condition: •...
  • Page 23 FIRECLASS PRECEPT EN13 EQUIPMENT: FIRECLASS PREC EN13 INST PUBLICATION: ISSUE No. & DATE: 22/07/2021 Engineer’s Select feature. [For use with MTL Table 1 – Motherboard Delay Switch Settings 5561 galvanic isolators]. Delay [Not EN54 compliant function.] Duration NONE 1 minute •...
  • Page 24: Repeater Interface B Configuration

    FIRECLASS PRECEPT EN13 EQUIPMENT: FIRECLASS PREC EN13 INST PUBLICATION: ISSUE No. & DATE: 22/07/2021 14.8 Configuring the Fire Routing, Fire • SW2-8 - Silent Zone Test: Protection and Fault routing O/Ps Select sounder response in One Man [Detector] To configure the Fire Routing Output to volt-free Test Mode: relay contacts, remove links J10, J11 and J12.
  • Page 25 FIRECLASS PRECEPT EN13 EQUIPMENT: FIRECLASS PREC EN13 INST PUBLICATION: ISSUE No. & DATE: 22/07/2021 • To set Day/Night Mode Off Time Pressing ENABLE (+) or DISABLE (-) toggles setting between D/N ON and D/N OFF. Press SELECT ↓, to access day/night OFF Time Set display: •...
  • Page 26: Able 2 - C1631 Setting Repeater Able 3 - C1631 Setting Repeater Able 4 - C1651 Clock Module Link Settings

    FIRECLASS PRECEPT EN13 EQUIPMENT: FIRECLASS PREC EN13 INST PUBLICATION: ISSUE No. & DATE: 22/07/2021 The backlight remains OFF. The panel indicates a 15.2 Configuring the Clock Module general fault and prevents the clock module from The Clock Module is configured by setting Link 1 being accessed by the user/engineer.
  • Page 27: Counter

    FIRECLASS PRECEPT EN13 EQUIPMENT: FIRECLASS PREC EN13 INST PUBLICATION: ISSUE No. & DATE: 22/07/2021 15.4 C1651 Clock Module PCB Features Figure 10 llustrates the PCB features referred to elsewhere in the documentation Figure 10 – C1651 Clock Module PCB LK1 – Select...
  • Page 28: C1651 Clock Module 16. Mechanical , Electrical & E Specification

    FIRECLASS PRECEPT EN13 EQUIPMENT: FIRECLASS PREC EN13 INST PUBLICATION: ISSUE No. & DATE: 22/07/2021 Mechanical, Electrical & Environmental Specification Panel Repeater (AC powered) Mechanical Specification 2/4 zone 8 zone 16 zone 2, 4, 8 & 16 zone Size [mm] Height:...
  • Page 29 FIRECLASS PRECEPT EN13 EQUIPMENT: FIRECLASS PREC EN13 INST PUBLICATION: ISSUE No. & DATE: 22/07/2021 Panel Repeater (AC powered) Battery Specification 2/4 zone 8 zone 16 zone 2, 4, 8 & 16 zone Battery charger output: [Temperature compensated float 1.5A 1.5A charger] 28.0V ±0.1V@-5°C...
  • Page 30: Egulation

    FIRECLASS PRECEPT EN13 EQUIPMENT: FIRECLASS PREC EN13 INST PUBLICATION: ISSUE No. & DATE: 22/07/2021 Construction Products Regulation Tyco Fire & Security GmbH Victor von Bruns-Strasse 21 8212 Neuhausen am Rheinfall Switzerland 2797-CPR-656146 0086-CPR-748117 DoP-2015-4145 EN/BSEN 54-2 Control and indicating equipment for fire detection and fire alarm systems for buildings...
  • Page 31 FIRECLASS PRECEPT EN13 EQUIPMENT: FIRECLASS PREC EN13 INST PUBLICATION: ISSUE No. & DATE: 22/07/2021 Tyco Fire & Security GmbH Victor von Bruns-Strasse 21 8212 Neuhausen am Rheinfall Switzerland 2797-CPR-656146 0086-CPR-748117 DoP-2015-4145 EN/BSEN 54-4 Power supply equipment for fire detection and fire alarm systems for buildings...
  • Page 32 FIRECLASS PRECEPT EN13 EQUIPMENT: FIRECLASS PREC EN13 INST PUBLICATION: ISSUE No. & DATE: 22/07/2021 © 2021 Johnson Controls . All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.