Output Relay Replacement (on receiver)
1. Remove the receiver power supply module as directed in the Power Supply Module Removal section.
2. Remove the screws holding the output relay board to the power supply module. Two holes in the orange
rail ease access to the screws. (see figure 4-10).
3. Carefully disconnect and remove the output relay board.
CONNECTOR PIN DAMAGE
Replace 3-output relay board with care to avoid damaging pins.
Failure to comply with these instructions may result in product damage.
4. Positioning the connectors like the first output relay board, install a new output relay board (same part
number).
Figure 4-10 Output Relay Replacement
5. Perform the operational test to ensure proper functional readiness.
107062-12 EN FR26 GLO 501 Printed in France