Fire and flame detectors
multi-spectrum infrared / ultraviolet electro-optical multi-spectral digital
wideband ir sensor with ultraviolet phototube (33 pages)
Page 1
Installation Guide and Operating – Manual FSX™ Fire and Flame Detectors Model FS24X™ FS24X QuadBand Triple IR™ Multi-Spectrum Infrared Electro-Optical Multi-Spectral Digital WideBand IR Sensor Radiant Energy Fire and Flame Detector...
Page 2
This manual is subject to change without notice. Copyright 2015 by Honeywell International Inc. While this information is presented in good faith and believed to be accurate, Honeywell disclaims the implied warranties of merchantability and fitness for a particular purpose and makes no express warranties except as may be stated in its written agreement with and for its customers.
The WideBand IR spectral radiant energy wavelengths sensed by the Quad (4) sensors span from approximately 0.4 to 5.5 microns for the FS24X. The Model FS24X Multi-Spectrum Fire and Flame Detectors are designed and Factory Mutual approved for use in Class Div.
-67° F to +221° F (-55° C to +105° C) 1.2.4 Performance Specifications Field of View: FS24X detectors have a cone of view of 90° horizontal and 80° vertical with the highest sensitivity on the central axis Sensitivity: One (1) sq. ft. heptane reference fire at 200 feet...
Installation Guide and Operating Manual Flame Performance Certification (See Sections 4.7.3 and 4.7.4 on page 28 and 29) 1.2.6 Agency Standard Certificate Notes LPCB EN 54-10:2002 +A1:2005 1175a/02 Sensitivity settings: Very High, High EN 54-10:2002 +A1:2005 0832-CPR-F0516 EN 54-10 Class 1 Honeywell...
FSC Windows® based PC Interface User can perform remote FSX Detector diagnostics, real-time status, Real-Time Graphing (RTG), SnapShot data recording, and downloading FirePic’s with Honeywell Analytics’ exclusive FSIM-2 ® USB Interface Unit and easy to use Windows based PC Software.
Detector’s field of view. 2. The installation shall take into account that the FS24X orientation should be with the base horizontal (see Figure 2-1) as the view angle in this direction is 90°. The vertical angle is 90°.
Page 9
Figure 2-5 CAUTION: Follow static protection procedures while handling the connectors and the wiring of the Module puck to the Detector. Use a wrist strap connected to earth ground. Honeywell...
1. Loosen the set screw on the enclosure lid (see Figure 2-6). Figure 2-6 2. Turn counterclockwise (CCW) to unscrew the enclosure lid (see Figure 2-7). Figure 2-7 3. Loosen the three captive screws on the Detector Module puck (see Figure 2-8). Figure 2-8 Honeywell...
Alarm COM 4-20mA Sink Figure 2-10 Fault NO Detector Puck, ( rear view Fault COM +24 VDC DC Return Contacts shown with no power applied Note: Do not attempt to open the Detector Module puck as this voids all warranties. Honeywell...
, check that the Detector is configured correctly for the specific B efore completing the installation application. The FSX Detectors Factory Default Settings are: Alarm Relay Outputs are Non-Latching and Normally De-Energized SW2-1 OFF SW2-7 OFF Detector Range / Sensitivity is Medium (2) SW2-2 OFF SW2-3 ON Honeywell...
Note: Honeywell Analytics FSX Detectors feature an automatic built-in “through the lens” test that verifies the cleanliness of its viewing window lens and test its internal electronics and software.
Page 15
Remember to disable the outputs, as a full functional test includes activating the ALARM outputs. A Honeywell Analytics Test Lamp must be used for this test (Section 4.4). Point the Test Lamp directly at the front of the Detector (on axis as much as possible, within a distance of about 1 to 25 feet). Activate the Test Lamp by pressing and holding its pushbutton.
Infrared (IR) consists of spectral wavelengths longer than the color red. The IR range for fire detection, which is invisible to the human eye, is from about 700 nanometers to 7000 nanometers (0.7 to 7.0 microns). Honeywell Analytics’ FS24X Fire Detectors utilize a NearBand IR™ portion of the spectrum from approximately 185 to 260 nanometers and a WideBand IR portion from approximately 0.7 to 3.3 microns.
Page 17
Auxiliary Relay SW2-4 SW2-5 No Verify Time 5 Sec Verify Time During a fire, model FS24X-911-24-5 10 Sec Verify Time detectors will alarm in non-latching 20 Sec Verify Time mode and will unlatch when the fire decreases. If the condition persists...
Installation Guide and Operating Manual LED Status Indicators The Model FS24X Detector uses three (3) separate, bright LED’s to indicate the Detector’s status. The Green LED blinks (flashes) once every ten (10) seconds to indicate a Normal, safe operational condition (i.e.
Dirty Window Lens (Yellow LED flashes, the Yellow LED is ON [solid] for all other Faults). Maintenance After the FS24X Detector is installed and commissioned, there is little maintenance required. However, a complete “end-to-end” test of the entire fire detection system should be performed periodically depending on the application.
Honeywell Analytics warrants its Products against defects in material and workmanship under normal use and service for a period of three years from the date of shipment as described herein. Honeywell Analytics, at its option, will repair or replace, at no charge, such products found to be defective during the warranty period provided that they are returned in accordance with the terms of this warranty.
2 = Relays / HART Communication Application 1 = General Applications Manufacturer’s Code 2 = Standard Honeywell Analytics Detector - 110° Field of View (-1 has been replaced by -2) 9 = Standard Honeywell Analytics Detector - 90° Field of View EXAMPLES: FS24X-911-211 QuadBand Triple IR Detector, 90°...
TL-2055 Test Lamp is as follows. If the FS24X set at Highest Sensitivity alarms to a fully charged TL-2055 Test Lamp at a distance between 1 and 25 feet, then the FS24X is in normal operating condition.
EN54-10 standard. Additional Performance Specifications 4.6.1 Flame Response Sensitivity The following table provides FS24X typical INDOOR response times and distance to various fuels: FS24X QuadBand (Very High [4] Sensitivity) Typical Fuel Fire Size...
1. Cable shield must be grounded at one end only, at the Control Panel. Coil and tape cable shield at the Detector end. 2. Set SW3 (rotary switch) to position one (1) for Source current wiring. 3. Set SW3 (rotary switch) to position zero (0) for Sink current wiring. Honeywell...
Page 27
3. Fault relay contacts shown with no power applied. During normal operation and with no Fault, this relay will De-Energize and the N.O. (normally open) contacts will close. 4. EOL (End-Of-Line) device shall be installed as required and supplied by the Fire Alarm Panel. Honeywell...
Honeywell Analytics Asia Pacific Co., Ltd. #701 Kolon Science Valley (1) 43 Digital-Ro 34-Gil, Guro-Gu Seoul, 152-729 Korea Email: analytics.ap@honeywell.com Internet These Honeywell websites may be of interest to Industry Solution customers. Honeywell Organization Corporate www.honeywell.com Honeywell Analytics www.honeywellanalytics.com Telephone Contact us by telephone at these numbers.
Need help?
Do you have a question about the FS24X and is the answer not in the manual?
Questions and answers