Installation Guide and Operating Manual Fire Sentry FS7-2173-2RP Fire Detector Stand-Alone, Leak-Proof, Digital, Electro-Optical With 20-foot Pigtail Cable...
Page 2
Fire Sentry FS7-2173-2RP Fire Detector Installation Guide and Operating Manual MAN0934_V1_1515001_Rev F_08-12...
Fire Sentry FS7-2173-2RP Fire Detector Installation Guide and Operating Manual MAN0934_V1_1515001_Rev F_08-12 APPROVALS FS System 7 has been manufactured in compliance with the requirements of the ISO-9001 standard and has been approved by: Factory Mutual (FM) CE Compliant SECTION 1: INTRODUCTION 1.1 FS7-2173-2RP Overview...
Fire Sentry FS7-2173-2RP Fire Detector Installation Guide and Operating Manual MAN0934_V1_1515001_Rev F_08-12 2.2 Detector Installation 2.2.1 MOUNTING BRACKET LOCATION a. The Fire Detector has a 120-degree conical Field-of-View (viewing angle). It is recommended the Detector be positioned with the primary fire threat location along in the axis of the Detector’s Field-of-View.
Fire Sentry FS7-2173-2RP Fire Detector Installation Guide and Operating Manual MAN0934_V1_1515001_Rev F_08-12 3.1.3 Detector Self-Test The Detector automatically performs an internal Self-Test every 10 minutes to check the integrity of operation. The Detector is still fully functional and able to Alert/Alarm to a fire or Fault while Self-tests are occurring.
Fire Sentry FS7-2173-2RP Fire Detector Installation Guide and Operating Manual MAN0934_V1_1515001_Rev F_08-12 4.2 Routine Maintenance and Calibration The Detector has no calibration requirements or field calibration options. It is recommended to test the Detector according to a periodic scheduled. When operated in a clean room environment, the window viewing area is expected to remain clean.
Fire Sentry FS7-2173-2RP Fire Detector Installation Guide and Operating Manual MAN0934_V1_1515001_Rev F_08-12 SECTION 5: DETECTOR CABLE WIRING Table 1: Pigtail Wiring Data Wire Wire Description Color Number BLACK 24 V Return (-) Supply + 24 VDC Supply GREEN FireBus RS-485 Digital Data A Signal...
Fire Sentry FS7-2173-2RP Fire Detector Installation Guide and Operating Manual MAN0934_V1_1515001_Rev F_08-12 SECTION 6: ORDERING INFORMATION DESCRIPTION PART NUMBER FS7-2173-2RP Fire Detector: The Stand-alone FS7 Electro-Optical Fire FS7-2173-2RP Detector for wet benches with Wide Band Infrared Spectral Sensor Array; operating temperature range is 0 to +70 ºC (+ 32ºF to +158ºF) The standard cable length is ten (10) feet.
Fire Sentry FS7-2173-2RP Fire Detector Installation Guide and Operating Manual MAN0934_V1_1515001_Rev F_08-12 INDEX Calibration ........... 5 Normal Operation......... 3 Detector Ratings ............1 Internal problem........5 Relay Detector Test ..........4 Fault ............3 Fault ............3 Replacement Relay ............3 Detector ...........
Page 12
Asia Pacific Data may change, as well as legislation, and you are strongly advised to Honeywell Analytics Asia Pacific obtain copies of the most recently issued regulations, standards, and #508, Kolon Science Valley (I) guidelines.
Need help?
Do you have a question about the Fire Sentry FS7-2173-2RP and is the answer not in the manual?
Questions and answers