Fire and Flame Detectors
Model FS20X™ Series
FS20X WideBand IR™ / UV
Multi-Spectrum Infrared / Ultraviolet Electro-Optical Multi-Spectral Digital
WideBand IR Sensor with Ultraviolet Phototube
Radiant Energy Fire and Flame Detector

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell FS20X Series

  • Page 1 Installation Guide and Operating Manual ™ Fire and Flame Detectors Model FS20X™ Series FS20X WideBand IR™ / UV Multi-Spectrum Infrared / Ultraviolet Electro-Optical Multi-Spectral Digital WideBand IR Sensor with Ultraviolet Phototube Radiant Energy Fire and Flame Detector...
  • Page 2 This manual is subject to change without notice. Copyright 2015 by Honeywell International Inc. While this information is presented in good faith and believed to be accurate, Honeywell disclaims the implied warranties of merchantability and fitness for a particular purpose and makes no express warranties except as may be stated in its written agreement with and for its customers.
  • Page 3: Table Of Contents

    4.6.2 False Alarm Immunity .......................... 24 4.7 Drawings ................................25 4.7.1 Outline and Dimensions ........................25 4.7.2 Wiring and Terminal Connections ......................26 4.7.3 BRE Detector Labels ..........................28 4.7.4 EN54 Detector Labels ........................... 29 INDEX ..................................29 CONTACT HONEYWELL ANALYTICS ........................30 Honeywell...
  • Page 4: Section 1: Introduction

    2. The ten (10) pin DIP switch (SW1) is used for:  Selecting a unique digital address (128 choices).  Factory Use 3. The ten (10) position Rotary switch allows selection of the analog and digital communication protocol. Figure 1-2 FS20X Detector Puck, ( rear view Honeywell...
  • Page 5: Detector Technical Specifications

    T6: Ta = -40°C to +60°C Heater circuit turns ON only when temperature drops below zero degrees Fahrenheit (-17° C) The supply connection wiring shall be rated at least 10°C above the rated service temperature (120°C for T4 applications and 85°C for T5 applications) Honeywell...
  • Page 6: Flame Performance Certification

    Installation Guide and Operating Manual // Model FS20X™ Series Flame Performance Certification (See Section 4.7.3 on Pages 31) 1.2.6 Agency Standard Certificate Notes LPCB EN 54-10:2002 +A1:2005 1175a/01 Sensitivity settings: Very High, High, Medium EN 54-10 Class 1 EN 54-10:2002 +A1:2005 0832-CPR-F0515 Honeywell...
  • Page 7: Features & Benefits

     FSC Windows® based PC Interface User can perform remote FS20X Detector diagnostics, real-time status, Real-Time Graphing (RTG), SnapShot data recording, and downloading FirePic’s with Honeywell Analytics’ exclusive FSIM-2 ® USB Interface Unit and easy to use Windows based PC Software.
  • Page 8: Applications

    Commercial and Military Aircraft Hangars Engine Test Cells Marine Engine Rooms Marine Terminals Paint and Solvent Storage Power Plants Product Storage Terminals Rail and Truck Loading and Unloading Terminals Silane Gas Cabinets Silane Gas Manufacturing Hydrogen Plants Hydrogen Storage General Warehouses Honeywell...
  • Page 9: Section 2: Installation

    10:2002, an angle of ±40° (80°) from 0° (where 0° is the orientation of the detector in the same axes as the flame source) should not be exceeded, based on lab testing at a distance of approximately 5.3 ft (1.6 m). Honeywell...
  • Page 10: Opening The Detector

    Detector. Use a wrist s strap connec cted to earth ground. Open ning the D etector It is necessary to remove the D Detector Mod ule “puck” fro om the enclos sure to access s the field con nnections. Honeywell...
  • Page 11 Loosen the set screw on the enclosure lid (see Figure 2-6). Figure 2-6 5. Turn counterclockwise (CCW) to unscrew the enclosure lid (see Figure 2-7). Figure 2-7 6. Loosen the three captive screws on the Detector Module “puck” (see Figure 2-8). Figure 2-8 Honeywell...
  • Page 12: Detector Connections

    Alarm COM 4-20mA Sink Fault NO Fault COM Figure 2-10 +24 VDC Detector Module “puck” (rear view) DC Return Contacts shown with no power applied Note: Do not attempt to open the Detector Module “puck” as this voids all warranties. Honeywell...
  • Page 13 Installation Guide and Operating Manual // Model FS20X™ Series Figure 2-11 Recommended Wiring Configurations Honeywell...
  • Page 14: Installation Practices

    : The Detector’s metal conduit plug by itself cannot make a weather-tight seal. Metal-to-metal IMPORTANT does NOT provide protection against the ingress of moisture. It is necessary to obtain an approved material to apply to the threads in order to maintain the “weather-proof” integrity and satisfy local/regional regulations. Honeywell...
  • Page 15 6. To ensure optimum performance, shield the detector face from intense bright light sources when first energized. The Detector is now ready for Power-Up. O n Power-Up, the Fault Relay will change status if the Factory Default Setting is used (Section 3.2). Honeywell...
  • Page 16: Start-Up And Commissioning

    Detector test “end to end”. Using an external hand-held test lamp ensures that the Detector has a clear unobstructed view of the threat area. Note: Honeywell Analytics FSX Detectors feature an automatic built-in "through the lens" test that verifies the cleanliness of its viewing window lens every three seconds and tests it internal electronics and software.
  • Page 17 Remember to disable the outputs, as a full functional test includes activating the ALARM outputs. A Honeywell Analytics Test Lamp must be used for this test (Section 4.4). Point the Test Lamp directly at the front of the Detector (on axis as much as possible, within a distance of about 1 to 25 feet). Activate the Test Lamp by pressing and holding its pushbutton.
  • Page 18: Section 3: Operation

    185 to 260 nanometers and 0.4 to 3.5 microns. Honeywell Analytics’ Detectors sense and measure the radiant energy generated by a fire at the speed of light.
  • Page 19 Figure 3-3 to configure SW3. Factory Use Only Figure 3-3 SW3 Factory Use Only Ten (10) Position Rotary Switch Factory Use Only Note: The Low Sensitivity range is not approved as compliant with the requirements of EN 54-10:2002. Honeywell...
  • Page 20: Normal Operation

     4-20 mA (source 20 mA) Auxiliary Output  RS-485 FireBus Alarm Notification  RS-485 ModBus Alarm Notification 1 This output is a Verified Alarm Output Figure 3-5 2 Only one active Alarm output from this group Red LED Location Honeywell...
  • Page 21: Fault Conditions

    Additionally, semi-annual or quarterly testing should be performed, using the correct Honeywell Analytics Test Lamp, to ensure the integrity of the entire fire protection system. The optical window (lens) of the Model FS20X Detector should be clean in order to ensure the Detector is operating properly at all times.
  • Page 22: Section 4: Appendix

    Honeywell Analytics warrants its Products against defects in material and workmanship under normal use and service for a period of three years from the date of shipment as described herein. Honeywell Analytics, at its option, will repair or replace, at no charge, such products found to be defective during the warranty period provided that they are returned in accordance with the terms of this warranty.
  • Page 23: Product Variations

    1 = Fire, Auxiliary & Fault Relays / 4-20mA / FireBus II / ModBus Application 1 = General Applications Manufacturer’s Code 2 = Standard Honeywell Analytics Detector – Full Window FS20X-211-22-2 MultiBand IR plus UV Detector, General Applications with Relays, 4-20mA Output, FireBus , 316 Stainless Steel Enclosure with M25 Conduit Entries, Class , Divisions 1 &...
  • Page 24: Digital Communication Options

    Some manufacturers claim that their detectors do not need remote testing with an external Test Lamp because it tests itself. Even though Honeywell Analytics Detectors also perform “through the lens” self-testing and tests themselves, Honeywell Analytics, in compliance with NFPA 72 codes, has developed portable test lamps for periodical “end-to-end”...
  • Page 25: Field Of View Restrictor

    < 2 Seconds n-Heptane 12 in X 12 in (0.3 m X 0.3 m) 200 ft (61.0 m) < 4 Seconds Silane 1/32 dia (0.8 mm) orifice, 12 in (0.3 m) Plume 50 ft (15.2 m) < 3 Seconds Honeywell...
  • Page 26: 4.6.2 False Alarm Immunity

    Source at 3 feet / 91.44 centimeters Pelican Flashlight 1 foot / 30.48 centimeters Fire at 200 feet / 60.96 meters Source at 3 feet / 91.44 centimeters Incandescent Lamp 1 foot / 30.48 centimeters Fire at 200 feet / 60.96 meters Honeywell...
  • Page 27: Drawings

    Installation Guide and Operating Manual // Model FS20X™ Series Drawings 4.7.1 Outline and Dimensions Figure 4-3 Outline & Dimesional Drawing for FS20X Figure 4-4 Outline & Dimesional Drawing for SM4 Honeywell...
  • Page 28: Wiring And Terminal Connections

    1. Cable shield must be grounded at one end only, at the Control Panel. Coil and tape cable shield at the Detector end. 2. Set SW3 (rotary switch) to position one (1) for Source current wiring. 3. Set SW3 (rotary switch) to position zero (0) for Sink current wiring. Honeywell...
  • Page 29 3. Fault relay contacts shown with no power applied. During normal operation and with no Fault, this relay will De-Energize and the N.O. (normally open) contacts will close. 4. EOL (End-Of-Line) device shall be installed as required and supplied by the Fire Alarm Panel. Honeywell...
  • Page 30: Bre Detector Labels

    FM/Canada/US ATEX, Stainless IRTM/UV FS20X 0832-CPR-F0515 +110ºC +75ºC +60ºC IECEX approval Steel -60ºC -60ºC -60ºC Label, FS24X-9, ss, with 0.020” 316 QuadBand 1175a/02 Matte Black FM/Canada/US ATEX, Stainless Triple IRTM 6095- FS24X- 0832-CPR-F0516 +110ºC +75ºC +60ºC IECEX approval Steel Honeywell...
  • Page 31: En54 Detector Labels

    Start-Up and Commissioning, 14 FireBus II, 21, 22 Hazardous Locations, 3, 14, 22 Temperature, 5, 19 Test Lamp, 12. 14, 15, 19, 22 Trouble, 19 Installation Practices, 12 Warranty Information, 20 weatherproof, 12 LEDs, green, 18 red 18 yellow 16, 18, 19 Honeywell...
  • Page 32: Contact Honeywell Analytics

    Honeywell Analytics Asia Pacific Co., Ltd. #701 Kolon Science Valley (1) 43 Digital-Ro 34-Gil, Guro-Gu Seoul, 152-729 Korea Email: analytics.ap@honeywell.com Internet These Honeywell websites may be of interest to Industry Solution customers. Honeywell Organization Corporate www.honeywell.com Honeywell Analytics www.honeywellanalytics.com Telephone Contact us by telephone at these numbers.
  • Page 33 Installation Guide and Operating Manual // Model FS20X™ Series 1998M0902 Revision C September 2015 © 2015 Honeywell International Inc.