SPA memory parameter
Send:
SPA
Transmitted parameters such as CFIx<>, CFOx<>, TMRx<> and CRL<> are not immediately
permanently stored in the EEPROM of the VoE-IOBox. Only with the command SPA are the
parameters stored permanently and are then still available after a restart.
EXCEPTION CIP<> is stored immediately.
CFI/RCFI Setting the inputs IN1...6
Write:
CFI1<PORT,EVENT,MODE,Debounce time>
_CFI1<PORT,EVENT,MODE,Debounce time>
CFI1<0..4,0..4,0..1,0..999>
CFI1<0..4,0..4,0..1,0..999>
CFI1<0..4,0..4,0..1,0..999>
CFI1<0..4,0..4,0..1,0..999>
CFI2<x,x,x,xxx>
CFI3<x,x,x,xxx>
CFI4<x,x,x,xxx>
CFI5<x,x,x,xxx>
CFI6<x,x,x,xxx>
Technisches Handbuch
Version 5.2
Answer: SPA
Specifies the output to be switched.
0 = not assigned to any output, 1 = OUT1, 2 = OUT2, 3 =
OUT3, 4 = OUT4
0 = Input static. Output remains on as long as the input is
present.
1 = positive edge.
Output switches on with rising edge for the time programmed
with TMR1<...>.
2 = negative edge.
Output switches on with falling edge for the time programmed
with TMR1<...>.
3 = positive edge.
Output switches on/off with rising edge (impulse relay).
4 = negative edge.
Output switches on/off with falling edge (impulse relay).
0 = polling input.
1 = push input.
If the input state changes, INP1<0> or INP1<1> is transmitted.
0..999 ms debouncing for IN1.
see CFI1<x,x,x,xxx>
see CFI1<x,x,x,xxx>
see CFI1<x,x,x,xxx>
see CFI1<x,x,x,xxx>
see CFI1<x,x,x,xxx>
Technical data
Answer: none
Answer: „ACK"