Connecting The Failsafe Alarm Relay - Siemens RUGGEDCOM RS1600F Installation Manual

Rugged ethernet switches
Hide thumbs Also See for RUGGEDCOM RS1600F:
Table of Contents

Advertisement

Figure 2.10
2.3

Connecting the Failsafe Alarm Relay

The failsafe relay can be configured to latch based on alarm conditions. The NO
(Normally Open) contact is closed when the unit is powered and there are no active
alarms. If the device is not powered or if an active alarm is configured, the relay
opens the NO contact and closes the NC (Normally Closed) contact.
Note
Control of the failsafe relay output is configurable through RUGGEDCOM RS1600F .
One common application for this relay is to signal an alarm if a power failure
occurs. For more information, refer to the RUGGEDCOM RS1600F User Guide for the
RUGGEDCOM RS1600F.
The following shows the proper relay connections.
1
2
3
Figure 2.11
RUGGEDCOM RS1600F
Installation Manual, 01/2021, C79000-G8976-1014-03
Dual AC/DC Power Supply
1
2
3
Normally Closed Terminal
Common Terminal
Normally Open Terminal
Failsafe Alarm Relay Wiring
2.3 Connecting the Failsafe Alarm Relay
Installing Device
13