Siemens RUGGEDCOM RS1600F Installation Manual page 37

Rugged ethernet switches
Hide thumbs Also See for RUGGEDCOM RS1600F:
Table of Contents

Advertisement

Certification
6.2 EMC and Environmental Type Tests
EMC Type Tests per IEC 61850-3
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-29
IEC 61000-4-11
IEC 61000-4-12
IEC 61000-4-16
IEC 61000-4-17
IEC 60255-5
28
Test
Description
ESD
Radiated RFI
Burst (Fast
Transient)
Surge
Induced
(Conducted)
RFI
Magnetic Field
Voltage Dips
and Interrupts
Damped
Oscillatory
Mains
Frequency
Voltage
Ripple on DC
Power Supply
Dielectric
Strength
HV Impulse
Enclosure
Contact
Enclosure Air
Enclosure Ports
Signal Ports
± 4 kV @ 2.5 kHz
DC Power Ports
AC Power Ports
Earth
Ground Ports
Signal Ports
± 4 kV Line-to-Earth,
± 2 kV Line-to-Line
DC Power Ports
± 2 kV Line-to-Earth,
± 1 kV Line-to-Line
AC Power Ports
± 4 kV Line-to-Earth,
± 2 kV Line-to-Line
Signal Ports
DC Power Ports
AC Power Ports
Earth
Ground Ports
Enclosure Ports
40 A/m Continuous,
1000 A/m for 1 s
DC Power Ports
30% for 0.1 s, 60% for
0.1 s, 100% for 0.05 s
AC Power Ports
30% for 1 Period,
60% for 50 Periods
100% for 5 Periods,
100% for 50 Periods
Signal Ports
2.5 kV Common, 1 kV
Differential Mode @ 1 MHz
DC Power Ports
2.5 kV Common, 1 kV
Differential Mode @ 1 MHz
AC Power Ports
2.5 kV Common, 1 kV
Differential Mode @ 1 MHz
Signal Ports
30 V Continuous, 300 V for 1 s
DC Power Ports
30 V Continuous, 300 V for 1 s
DC Power Ports
Signal Ports
2 kVAC  (Fail-Safe Relay output)
DC Power Ports
AC Power Ports
Signal Ports
5 kV  (Fail-Safe Relay Output)
DC Power Ports
Test Levels
± 8 kV
± 15 kV
20 V/m
± 4 kV
± 4 kV
± 4 kV
10 V
10 V
10 V
10 V
10%
1.5 kVDC
2 kVDC
5 kV
RUGGEDCOM RS1600F
Installation Manual, 01/2021, C79000-G8976-1014-03
Severity
Levels
4
4
x
x
4
4
4
4
3
4
3
3
3
3
 
 
 
 
3
3
3
4
4
3
 
 
 
 
 

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic net ruggedcom rs1600f

Table of Contents