Common Specifications; Montage Mécanique - IMO iDrive-EDX Series Quick Reference Manual

Table of Contents

Advertisement

Available languages

Available languages

Common specifications

Output Frequency range
0~200Hz
Starting torque
100%/3Hz (Vector mode)
Speed control range
1:50 (Vector mode )
Speed control accuracy
±0.5% (Vector mode)
Setting resolution
Digital : 0.1Hz (0.~99.9Hz) / 1Hz(100~200Hz); analogue: 0.06Hz / 60Hz
Keypad setting
Set directly with
Display / Indication
7 segment*3. Displays frequency / DC voltage / output voltage / output current
inverter parameters / alarm log / software versions / PID feedback control
External signal setting
• External variable resistors / 0-10V / 4-20mA
• Performs up / down control (Motorised Pot.) with multi-function programmable
input on the terminal base
Frequency limit functions
Possible to set Upper and Lower frequency limits, and two-stage skip-frequencies
Carrier frequency
4~16KHz (default 10KHz, above 10KHz with de-rating)
V/F pattern
Select 6 fixed patterns 50Hz / 60Hz or 1 user programmable pattern
Acc/dec control
Two independent sets of accel / decel ramps (0.9~999s)
Multi-function analogue output
6 functions (refer to F26 description)
Multi-function input
19 functions (refer to F11~F14 description)
Multi-function output
16 functions (refer to F21 description)
DI (Digital input)
Selectable NPN / PNP: 4 inputs (S1~S4) as standard; 2 expansion inputs
(S5~S6) available on option card
DO (Digital output)
1*Relay output as standard SPST. --- selectable as multi-function output
1* Optional external multi-function output (open collector transistor 24V, 600mA)
AI (analogue input)
Set speed command and PID feedback signal (speed, PID, 4~20mA / 0~10V)
or MFIT S7 [MFIT=multi-function input terminal]
Other functions
Instantaneous power loss restart, Speed search, auto-restart, DC brake, torque
boost, 2 / 3 wire control and PID control
Communication control
• RS485 Option card: Modbus RTU / ASCII modes, 4800~38400 bps,
max 254 stations
• PC / PDA software
Operation temperature
-10~50˚C (inside enclosure) IP20; -10~40 IP65
Storage temperature
-20~60˚C
Humidity
0-95% RH (non condensing)
Vibration immunity
1G (9.8m/s
EMC
Built-in: First Environment, Unrestricted Distribution (Class B)
External: First Environment, Restricted Distribution (Class A)
In accordance with EN61800-3
LVD
Conforming to EN50178
Enclosure
IP20
Safety Class
UL508C
1
12
keys of the potentiometer VR on the keypad
2
)
Nomenclature
CAUTION
Manipuler le iDrive uniquement hors tension
Model:
EDX-040-21-E
Motor Rating: 0.5HP / 0.4KW
INPUT:
AC 1 phase 50 / 60Hz
VOLTAGE:
OUTPUT:
AC 3 phases 0 – 200Hz
VOLTAGE:
IP20 / UL Open Type (rated -10˚C to 50˚C Ambient)
IMO Precision Controls Ltd
ATTENTION: CE PRODUIT DOIT ETRE MIS A LA TERRE!
EDX
-
040
-
2
iDrive
Power (kW)
0.2
020
0.4
040
0.75
075
1.5
150
2.2
220
100V
1
200V
2
400V
4
Montage mécanique
Un iDrive EDX standard en boîtier IP est destiné à être câblé dans une armoire métallique reliée
à la terre. La température ambiante à l'intérieur de l'armoire ne doit pas excéder plus de 50°C sinon
la durée de vie du variateur sera diminuée. Si nécessaire prévoir un filtre plus un ventilateur afin de
faire baisser la température dans l'armoire. Le variateur doit être monté verticalement sur une plaque
métallique. Le variateur peut être fixé soit par les 4 trous de fixation soit sur rail DIN avec un
adaptateur.
200 – 240V (+10%, -15%)
I
: 5.4A
RMS
0 - V
I
: 3.1A
IN
RMS
1
-
E
Enclosure
IP65 étanche à l'eau
N4S
et à la poussière
IP65 étanche à l'eau
N4
et à la poussière
IP20
Filtre intégré
E
EMC Pas de filtre
1
1Phase
3
3 Phase
13

Advertisement

Table of Contents
loading

Table of Contents