19
Press 'DSP/FUN' key. Display shows
20
Press 'DATA/ENTRY' key. Display shows
21
Press
key 1 time. Display shows
22
Press 'DATA/ENTRY' key. New data is stored, display flashes
23
Press
key one time. Display shows
24
Press 'DATA/ENTRY' key. Display shows
25
Press
key 2 times. Display shows
26
Press 'DATA / ENTRY' key. New data is stored; display flashes
27
Press 'DSP / FUN' key. Display flashes
depending on position of external potentiometer)
28
Check that it is safe to operate the motor.
29
Set low output frequency by external potentiometer
30
Close the switch / relay connected between terminals 4 (S1) and 8 (COM)
31
Motor accelerates to frequency set by external potentiometer.
32
Check direction of motor is correct. If incorrect, STOP motor and remove power from
iDrive. When display clears, change-over any two of the three motor connections T1,T2,T3.
33
When all connections are made, replace cover and continue with any further parameter
changes required for compatibility with the application.
Note 2: Some parameters can not be changed when motor is operating.
See installation manual for more details.
10
A 0 0
(keypad RUN / STOP keys)
0 0 0
(RUN / STOP control from terminals)
0 0 1
then
8 8 8
A 0 0
A 0 1
(keypad
keys)
0 0 0
(speed reference from terminal 10 (AIN)
0 0 2
then
8 8 8
A 0 1
/
(the new output frequency
0 0 . 0
5 0 . 0
If in doubt consult a
qualified electrical engineer
or your iDrive supplier
Individual model specifications
iDrive 100V models
020
Horse power (HP)
0.25
Suitable motor capacity (kW)
0.2
Rated output current (A
)
1.7
RMS
Rated capacity (kVA)
0.53
Input voltage range (V)
1PH 100~120V+10%, -15%(50/60Hz)
Output voltage range (V)
Input current (A
)
7.1
RMS
Net weight (Kg)
0.62
Allowable momentary power loss time(s)
1.0
Enclosure
iDrive 200V models
020
Horse power (HP)
0.25
Suitable motor capacity (kW)
0.2
Rated output current (A
)
1.7
RMS
Rated capacity (kVA)
0.53
Input voltage range (V)
200~240V+10%, -15%(50/60Hz)
Output voltage range (V)
Input current (A
)
4.3
RMS
Net weight (Kg)
0.71
Allowable momentary power loss time(s)
1.0
Enclosure
iDrive 400V models
075
Horse power (HP)
1
Suitable motor capacity (kW)
0.75
Rated output current (A
)
2.3
RMS
Rated capacity (kVA)
1.7
Input voltage range (V)
3PH 380~480V+10%, -15%(50/60Hz)
Output voltage range (V)
Input current (A
)
3.0
RMS
Net weight (Kg)
1.68
Allowable momentary power loss time(s)
1.0
Enclosure
EDX-xxx-11
040
075
0.5
1
0.4
0.75
3.1
4.2
0.88
1.60
3PH 0~240V
12.2
17.9
0.68
0.72
1.0
1.0
IP20
EDX-xxx-21(-E)
EDX-xxx-23
040
075
150
220
020
040
075
0.5
1
2
3
0.25
0.5
1
0.4
0.75
1.5
2.2
0.2
0.4
0.75
3.1
4.2
7.5
10.5
1.7
3.1
4.2
0.88
1.60
2.90
4.00
0.53
0.88
1.60
1PH
3PH
200~240V+10%, -15%(50/60Hz)
3PH 0~480V
5.4
10.4
15.5
21
3.0
4.0
6.4
0.73
0.73
1.25
1.3
0.61
0.61
0.66
1.0
1.0
2.0
2.0
1.0
1.0
1.0
IP20
EDX-xxx-43(-E)
150
220
Standard models
2
3
1.50
2.2
3.8
5.2
2.9
4.0
Non-standard models
(special order only)
3PH 0~480V
4.8
6.6
1.70
1.73
2.0
2.0
IP20
150
220
2
3
1.5
2.2
7.5
10.5
2.90
4.00
9.4
12.2
0.95
1
2.0
2.0
11