Operating; Accessories; Maintenance; Warranty - oventrop Regufloor HX Installation And Operating Instructions For The Specialised Installer

Control unit with heat exchanger for surface heating systems
Table of Contents

Advertisement

Available languages

Available languages

7 Operation
7.1 Bleeding the system
Before initial operation, the system must be filled and
bled with due consideration of the permissible ope-
rating pressures.
7.2 Setting
Hydronic balancing is carried out at the presettable
valve insert of the regulating valve "Hycocon HTZ" in
the supply pipe of the primary side.
Set the corresponding flow temperature for the se-
condary circuit at the handwheel of the temperature
controller (control range 20 - 50 °C).
7.3 Correction factors for mixtures of water and
glycol
The correction factors of the manufacturers of the an-
tifreeze liquids have to be considered when setting
the flow rate.

8 Accessories

The Oventrop ball valves:
3
– 1406383 DN 20 G
4
– 1406384 DN 25 G 1 F x G 1 M
can be screwed onto the control unit for the isolation
of the supply and the return pipe.
The accessories can be found in the catalogue.

9 Maintenance

The control unit is maintenance-free.

10 Warranty

Oventrops warranty conditions valid at the time of
supply are applicable.