The minimum maintenance space requirements of the unit are shown in
Note:
These spaces are used for daily maintenance of the unit.
The front door of the unit is defined as the side with the display screen, and the side opposite the front door is the rear door.
The main units that are installed between the rows, only require maintenance space at the front and rear sides.
In case of a special application, consult Vertiv local representative.

2.3. Unpacking and Inspection

2.3.1. Transportation and Handling

1. When transporting, the priority shall be given to rail or water transportation. If user choose road transportation then a
road with better road conditions should be select to prevent excessive bumps.
2. Vertiv™ Vertiv™ Liebert® XDC unit is heavy. Refer
electric forklifts are required for unloading and handling.
3. When transporting, transport the unit to the place closest to the installation site.
the unit and the fork should be at the center of gravity to prevent tipping of the unit.
Vertiv™ | Liebert® XDC | User Manual
Table 2-1 Minimum Maintenance Space (unit: mm)
Location
Minimum Maintenance Clearance
Front door
600 mm
Rear door
600 mm
Display screen side
600 mm
Table 2-3
Figure 2-2 Forklift Position to Lift the Unit
Table
2-1.
for weight parameters. Mechanical handling tools, such as
Figure 2-2
illustrates the forklift lifting
10