Liebert Vertiv GXT5 Installer/User Manual page 115

Table of Contents

Advertisement

MODEL GXT5-
1500IRT2UXL*
1500IRT2UXLE
2000IRT2UXL*
2000IRT2UXLE
RATING
1500 VA/1500 W
2000 VA/2000 W
Output AC
Output Receptacles
C13 × 8
Voltage
200/208/220/230/240 VAC (user-configurable); ±3%
Waveform
Sine wave
Utility (AC) Model
>200% for 250 ms; 150-200% for 2 seconds
Overload
125-150% for 50 seconds; 105-125% 60 seconds
Internal Battery Charger
Charger Current, A
default 2.2 A; Maximum 8 A
Battery Parameters
Type
Valve-regulated, non-spillable, lead acid
Qty×V×Rating
4 × 12V × 9.0 Ah
Battery Mfr./Part#
LEOCH DJW12-9.0
Back-up time
See
Battery Run Times
on
page
119.
3 Hours to 90% capacity after full discharge with 100% load till UPS auto-shutdown (Internal
Recharge Time
Batteries Only)
Bypass Parameters
Upper-limit selections
+10%, +15%, +20%; default +10%.
Lower-limit selections
-10%, -15%, -20%; default -15%
Disable-bypass operation
When the input frequency prevents synchronous operation.
Environmental Requirements
Operating Temperature,
+32 to +122 (0 to 50); Operating temperature may be increased to 122 °F (50 °C with a 10%
°F (°C)
derating of the output power)
Storage Temperature, °F
-4 to +140 (-20 to 60) ( contain batteries will be from -15 to 40 °C.)
(°C)
Relative Humidity
0% to 95%, non-condensing
Operating Elevation
Up to 10,000 ft. (3000 m) at 77ºF (25ºC) without derating
<46 dBA max @ 3ft. (1 m) front and sides
<48 dBA max @ 3ft. (1m) front and sides <48
Audible Noise
<45dBA max @ 3 ft. (1 m) rear
dBA max @ 3 ft. (1 m) rear
Agency
Safety
UL-1778 (Fifth Edition), C-UL listed, IEC 62040-1: 2008 (First Edition) + Am 1:2013, EN 62040-1:2008+A1:2013
Transportation
ISTA Procedure 1A
Surge Immunity
ANSI C62.41 Category B
RFI/EMI
CISPR22 Class A (RFI)/ FCC Part 15 (Class A)
*Only these models are available in the ASIA PACIFIC region.
Vertiv | Liebert® GXT5™ | Installer/User Guide
107