8.4
MultiFlex I/O Board Pulse Limits - Standalone Version
Only
The MultiFlex board can read pulses at a maximum of 5HZ or 5PPS. The Energy Meter is capable of pulsing faster than
the 5PPS maximum that the MultiFlex board can read.
Pulses should be greater than 80mS in length at a maximum rate of 5HZ: Do not exceed 5PPS.
For Example:
• Values of 100, 250, or 500 will be read by the MultiFlex board.
• Values of 50, 25, or 10 will not be read by the MultiFlex board.
MultiFlex I/O Board Pulse Limits - Standalone Version Only
Solid-State Pulse Output • 19