m Notes for output wiring
External power supply
– Relay outputs
Use an external power supply of 30 V DC or less or 240 V AC or less for
loads.
– Transistor outputs
For driving the load, use a power supply of 5 to 30 V DC that can output
current two or more times the rated current of the fuse connected to the
load circuit.
Voltage drop
The voltage drop at ON of the output transistor is approx. 1.5 V. When driv-
ing a semiconductor element, carefully check the input voltage character-
istics of the applied element.
Response time
The transistor OFF time is longer under lighter loads. For example, with a
load of 40 mA at 24 V DC, the response time is approx. 0.3 ms. When
response performance is required under lighter loads, install a resistor in
parallel with the load to increase the load current of the output.
m Protection of the outputs
Protection circuit for load short-circuiting
When a load connected to the output terminal short-circuits, the printed
circuit board may be burn out.
Fit a protective fuse on the output circuit.
Protection circuit when inductive load is used
– Relay outputs
When an inductive (for example a relay or a solenoid) load is connected
to a DC voltage, connect a diode in parallel with the load.
Inductive
load
PLC output
Diode
(for commutation)
Use a diode (for commutation) having the following specifications:
– Reverse dielectric strength: over 5 times the load voltage
– Forward current: Load current or more
When an inductive load is switched by a relay output to an AC voltage,
connect a surge absorbing element (CR composite part, i.e. surge killer
and spark killer) in parallel with the load.
Inductive
load
PLC output
Surge absorber
Use a surge absorber having the following specifications:
– Rated voltage: 240 V AC
– Resistance value: 100 to 200 
– Electrostatic capacity: approx. 0.1 μF
– Transistor outputs
When an inductive (for example a relay or a solenoid) load is connected,
connect a diode in parallel with the load.
Transistor output (sink)
Inductive load
Y
Fuse
COM0
COM0
Transistor output (source)
Inductive load
Y
Fuse
+V0
+V0
Use a diode (for commutation) having the following specifications:
– Reverse dielectric strength: 5 to 10 times the load voltage
– Forward current: Load current or more

Terminal Layout

Input module
FX5-C16EX/D
Inputs
X0
X10
X1
X11
X2
X12
X3
X13
X4
X14
X5
X15
X6
X16
X7
X17
S/S
S/S
Inputs
X0
X10
X1
X11
X2
X12
X3
X13
X4
X14
X5
X15
X6
X16
X7
X17
S/S
S/S
PLC
PLC
Output modules
FX5-C16EYR/D-TS
Outputs
Y0
Y0
Y1
Y1
Y2
Y2
Y3
Y3
Y4
Y4
Y5
Y5
Y6
Y6
Y7
Y7
COM0
COM0
Outputs
Y10
Y10
Y11
Y11
Y12
Y12
Y13
Y13
Y14
Y14
Y15
Y15
Y16
Y16
Y17
Y17
COM1
COM1
FX5-C32EYT/D-TS
FX5-C32EYT/DSS-TS
Outputs
Outputs
Y0
Y10
Y0
Y10
Y1
Y11
Y1
Y11
Y2
Y12
Y2
Y12
Y3
Y13
Y3
Y13
Y4
Y14
Y4
Y14
Y5
Y15
Y5
Y15
Y6
Y16
Y6
Y16
Y7
Y17
Y7
Y17
COM0
COM0
+V0
+V0
Outputs
Outputs
Y0
Y10
Y0
Y10
Y1
Y11
Y1
Y11
Y2
Y12
Y2
Y12
Y3
Y13
Y3
Y13
Y4
Y14
Y4
Y14
Y5
Y15
Y5
Y15
Y6
Y16
Y6
Y16
Y7
Y17
Y7
Y17
COM1
COM1
+V1
+V1
Input/Output modules
FX5-C32ET/DS-TS
FX5-C32ET/DSS-TS
Inputs
Inputs
X0
X10
X0
X10
X1
X11
X1
X11
X2
X12
X2
X12
X3
X13
X3
X13
X4
X14
X4
X14
X5
X15
X5
X15
X6
X16
X6
X16
X7
X17
X7
X17
S/S
S/S
S/S
S/S
Outputs
Outputs
Y0
Y10
Y0
Y10
Y1
Y11
Y1
Y11
Y2
Y12
Y2
Y12
Y3
Y13
Y3
Y13
Y4
Y14
Y4
Y14
Y5
Y15
Y5
Y15
Y6
Y16
Y6
Y16
Y7
Y17
Y7
Y17
COM0
COM0
+V0
+V0
Mitsubishi Electric Europe B.V. /// FA - European Business Group ///
Germany /// Tel.: +49(0)2102-4860 /// Fax: +49(0)2102-4861120 ///
https://eu3a.mitsubishielectric.com