ZCS 1PH 1100TL User Manual

ZCS 1PH 1100TL User Manual

Grid-connected inverter

Advertisement

Quick Links

Grid-connected inverter
1PH 1100TL-3300TL-V3
Zucchetti Centro Sistemi S.p.A. - Green Innovation Division
Via Lungarno, 248 - 52028 Terranuova Bracciolini - Arezzo, Italy
tel. +39 055 91971 - fax. +39 055 9197515
innovation@zcscompany.com - zcs@pec.it – www.zcsazzurro.com
Reg. Pile IT12110P00002965 - Share Capital € 100,000.00 fully paid up
Reg. Impr. AR n.03225010481 - REA AR - 94189
ISO 9001 Certified Company - Certificate no. 9151 - CNS0 - IT-17778
User Manual

Advertisement

Table of Contents
loading

Summary of Contents for ZCS 1PH 1100TL

  • Page 1 Via Lungarno, 248 - 52028 Terranuova Bracciolini - Arezzo, Italy tel. +39 055 91971 - fax. +39 055 9197515 innovation@zcscompany.com - zcs@pec.it – www.zcsazzurro.com Reg. Pile IT12110P00002965 - Share Capital € 100,000.00 fully paid up Reg. Impr. AR n.03225010481 - REA AR - 94189...
  • Page 2: Table Of Contents

    Checks before installation..............................17 3.3. Installation tools ..................................19 3.4. Installation position ................................21 3.5. Moving the 1PH 1100TL-3300TL-V3 inverter ......................23 3.6. Installing the 1PH 1100TL-3300TL-V3 inverter ....................... 23 Electrical connections ....................................25 4.1. Electrical connections ................................26 4.2.
  • Page 3 Troubleshooting ..................................96 10.3. 4G adapter ....................................97 10.3.1. Installation ....................................98 10.3.2. Verification ..................................... 100 Warranty terms and conditions .............................. 103 3 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 4 Please check our website at http://www.zcsazzurro.com for the latest version. Technical support ZCS offers a support and technical consultancy service accessible by sending a request directly from the website https://www.zcsazzurro.com/it/support. The following toll-free number is available for the Italian territory: 800 72 74 64.
  • Page 5 This manual describes the assembly, installation, electrical connections, commissioning, maintenance and troubleshooting of the following AZZURRO inverters: 1PH 1100TL-V3 / 1PH 1600TL-V3 / 1PH 2200TL-V3 / 1PH 2700TL-V3 / 1PH 3000TL-V3 / 1PH 3300TL-V3 Keep this manual so that it is accessible at all times.
  • Page 6 Attention Note: provides important tips on the correct and optimal operation of the product. Note 6 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 7: Preliminary Safety Instructions

    Zucchetti Centro Sistemi S.p.A. declines all responsibility for damage to property or personal injury caused by incorrect use of the device. 7 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 8 DC switches of the generator. When exposed to the sun, the photovoltaic panels produce a voltage that can be Danger dangerous! 8 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 9 Attention Do not remove the information label or open the inverter. Otherwise, ZCS will not provide any warranty or maintenance. Note Operation Contact with the electrical grid or the terminal of the equipment may cause electrocution or fire! ...
  • Page 10: Symbols And Icons

    Ensure the correct DC input voltage; this must be below the maximum allowable DC voltage. Overvoltage can cause permanent damage to the inverter that is not covered by the warranty! Warning 10 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 11 Degree of protection of the equipment according to the IEC 70-1 standard (EN 60529 June 1997). Positive and negative polarities of the input voltage (DC). 11 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 12: Product Features

    2. Product features General information in this chapter Product dimensions The field of use and overall dimensions of the 1PH 1100TL-3300TL-V3 inverters are indicated in this section. Description of functions Describes how the 1PH 1100TL-3300TL-V3 inverters and their internal operating modules work.
  • Page 13 • Overall dimensions 1PH 2700TL-3300TL-V3 : LxWxH = 321 mm x 260.5 mm x 131.5 mm Figure 4 – Front, side and back view of the inverter and bracket 13 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00...
  • Page 14: Description Of Functions

    If enabled, the inverter can limit the amount of active power fed into the grid at the desired value (expressed as a percentage). 14 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 15 RS485 interface or via Wi-Fi. E. Software update A microSD card is used to update the firmware.  Wiring diagram Figure 6 – Block diagram of the 1PH 1100TL-3300TL-V3-L inverter 15 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev.
  • Page 16: Efficiency Curve

    2.3. Efficiency curve Efficiency curve for an Azzurro ZCS 1PH 3300 TL-V3 model Figure 7 – Efficiency curve for an Azzurro ZCS 1PH 3300TL-V3 inverter 16 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 17: Installation

     DO NOT install 1PH 1100TL-3300TL-V3 inverters near flammable materials.  DO NOT install 1PH 1100TL-3300TL-V3 inverters in an area where flammable or Danger explosive materials are stored. The housing and heat sink may become very hot while the inverter is running, DO NOT install the inverter in places where they may be touched inadvertently.
  • Page 18 2 M5 hexagonal screws 10 M6 flat washers 3 expansion plugs (1 spares) 5 self-tapping screws 1 user manual 2 warranty 18 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 19: Installation Tools

    Wire stripper To prepare the cables for wiring Adjustable spanner (opening To tighten the bolts greater than 32 mm) 19 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 20 To crimp the power cables To check the voltage and current Multi-meter values To mark the wall for better Marker pen fixing precision 20 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 21: Installation Position

    Protective clothing 3.4. Installation position Choose an appropriate installation location for the inverter. Follow the requirements below to determine the installation position. 21 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 22 Figure 10 – Requirements for installing multiple inverters For safety reasons, ZCS Spa and/or its partners may not carry out any technical repairs or maintenance work, or move the inverter from and to the ground if it is installed at a height of more than 180 cm from the ground.
  • Page 23: Moving The 1Ph 1100Tl-3300Tl-V3 Inverter

    3.5. Moving the 1PH 1100TL-3300TL-V3 inverter This section describes how to move the inverter correctly Open the packaging and remove the protective cover in polystyrene, insert your hands into the slots on both sides of the inverter and take a hold of it, as shown in figures 11 and 12.
  • Page 24 (not supplied with the kit). Figure 13 - Steps for mounting the inverter on the wall 24 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 25: Electrical Connections

    4. Electrical connections General information in this chapter This chapter describes the electrical connections of the 1PH 1100TL-3300TL-V3 inverter. Carefully read this section before connecting the cables. NOTE: Before making any electrical connections, ensure that the DC circuit breaker is switched off. Please note that the capacitors in the inverter may remain electrically charged after the DC circuit breaker has been switched off.
  • Page 26: Electrical Connections

    Figure 14 – Steps for connecting the cables 4.2. Ground cable connections (PGND) Connect the 1PH 1100TL-3300TL-V3 inverter to the ground electrode using ground protection cables (PGND). The inverter does not have a transformer, therefore the positive and negative polarities of the photovoltaic string do NOT need to be grounded. Otherwise, the inverter may fail.
  • Page 27 2. Install the crimped OT terminal and flat washer using the M5 screw in the hole located on the inverter heatsink, as shown in the figure; tighten the screw to a torque of 3 Nm using an Allen key. 27 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00...
  • Page 28: Connecting The Dc Input Power Cables

    The positive and negative terminals of the PV strings must be connected respectively to the positive and negative inputs of the input terminal block. 28 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 29 Table 1 – Recommended specifications for DC input cables The DC input connectors (MC4) are classified into positive and negative connectors, as shown in the figures below. 29 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 30 Make sure that the cables are secured so that they cannot be pulled out with a force of less than 400 N, as shown in Figure 20 30 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00...
  • Page 31 If not, the direct current may cause an Warning electric arc that could result in a fire 31 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 32: Connecting The Ac Output Power Cables

    >6 >6 >6 Cable (mm 16A/400V 16A/400V 25A/400V 25A/400V 25A/400V 25A/400V Switch Table 2 – Recommended specifications for AC output cables 32 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 33 150 meters. The figure below shows the relationship between the power loss in the cable, its length and the cross- section area. 33 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 34 AC output cable; the figure of the AC connector is shown below. Figure 25 – AC Output Connector 34 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 35 • Connect the line wire (brown) to the hole labelled “L”, and tighten the cable with an Allen key; • Connect the neutral wire (blue) to the hole labelled “N”, and tighten the cable with an Allen key; 35 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00...
  • Page 36 Disconnect the AC connector from the output terminal of the inverter, turning it in an anti-clockwise direction until the fixing device reaches its intended position, as shown below: Figure 30 - Disconnecting the AC output cables 36 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 37: Connecting The Communication Cables

    4.5. Connecting the communication cables The figure below shows the arrangement of the communication ports on the inverters 1PH 1100TL - 3300TL-V3. Figure 31 - Arrangement of communication ports Connecting the communication port Note: The wiring procedure is the same for the RS485 input, I/O input and CT input. This chapter describes the procedure for connecting the communication cables.
  • Page 38 4) Choose the terminal according to Table 4, connect the cables as shown in the labels and secure them using a flat screwdriver. Note: keep the unused terminals for future use. 38 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 39 5) Insert the terminal according to the printed label, then tighten the screws to secure the waterproof cover; turn the cable glands clockwise to tighten. Figure 35 – Closing the central door 39 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 40 Figure 36 – Closing the central door 40 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 41: Commissioning The Inverter

    Zucchetti Centro Sistemi S.p.A. shall not be held responsible for any consequences resulting from the incorrect selection of the country code. 41 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 42 If the inverter indicates the presence of any faults, refer to chapter 7.1 of this manual or contact the Zucchetti Centro Sistemi S.p.A. technical support. 42 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 43: Operating Interface

    Indicator lights:  Status light (GREEN) o Flashing: wait or status check o Steady: normal operation o Off: temporary or permanent error 43 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 44: Main Interface

     Total energy produced by the inverter AC grid disconnection error Figure 38 – Example of main screens on the display 44 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 45 At start up, the LCD screen displays “ZCS INNOVATION...,” as shown in the figure below, when the control board is correctly connected to the communication board, the LCD display will show the current status of the inverter, as shown in the figure below.
  • Page 46: Main Menu

    Long press (3 seconds) the button when you are in the main interface screen to enter the main menu, which will appear as follows: 46 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 47 “List of historical events” submenu. Long press the key to start the procedure; the display will show “OK” if the operation is successful. 47 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00...
  • Page 48 South Africa France Brazil AU-WA Poland Slovakia Dubai DEWG Germany BDEW Slovakia SSE Dubai DEWG MV Germany VDE Slovakia ZSD Taiwan 0126 48 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 49 In the current firmware version (V1.00), the languages available are: Chinese, English, Italian, German, French and Portuguese; future firmware updates may add new languages. 49 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 50 The user can change the value of the protection voltage directly from the LCD display. The user must first copy the TXT files to the SD card. These files can be requested from ZCS technical support. Select “12. Safety Voltage” and long press the key to enter the menu for setting the protection voltage. The display will show “Enter PWD!”;...
  • Page 51 The user can change the value of the insulation resistance directly from the LCD display. The user must first copy the TXT files to the SD card. These files can be requested from ZCS technical support. Select “14. Insulation” and long press the key to enter the menu for setting the insulation resistance. The display will show “Enter PWD!”;...
  • Page 52 5) The self-test will now start automatically; once completed, short press the key to display the self- test results, as shown in the figure. 52 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 53 53 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 54 5) The self-test will now start automatically; once completed, short press the key to display the self-test results, as shown in the figure. 54 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 55 55 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 56 “1. Enable 81.S1” and “2. Disable 81.S1” and select it by long pressing the key. The display will show “OK” if the setting is successful. 56 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00...
  • Page 57 ZCS S.p.A. accepts no responsibility deriving from the activation of one of the settings described above.
  • Page 58 From the “System Info” menu, short press the key to move it, and hold it down for a few seconds to enter the menu “11. Service Code.” Here you can see the currently installed firmware version. 58 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00...
  • Page 59 Note: the USB device is not supplied with the inverter and must be procured by the installer or customer. 59 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 60 PC with USB port Firmware update procedure 1. Switch off the ZCS inverter by first disconnecting the AC power supply via the switch installed on the system, and then disconnecting the DC power supply via the switch located on the side of the inverter or switch off the system’s disconnecting switch.
  • Page 61 DSP2 Update ARM Update 9. Check that the inverter completes the update correctly and that “ZCS INNOVATION” appears on the display; the inverter will then start normally. If the update was not successful, one of the following messages will appear on the display: “Commun Err”, “UPDATE DSP1 FAIL” or “UPDATE DSP2 FAIL”;...
  • Page 62: Troubleshooting And Maintenance

    The grid voltage is too ID02 GridUVP return to its normal operating state low. when the electrical grid is restored to 62 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 63 PV string by adjusting the number of photovoltaic modules mounted in series, making sure that it falls within the input voltage range 63 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 64 5 protection to be minutes, then turn on the DC activated. disconnecting switch again. Check 64 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 65 The DCI is too high. Section 6.3 (C). “6. Input Mode” of this user manual; if this setting is not correct, change it 65 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 66 ID51 ConsistentFault_DCI breaker (DCI) between the master DSP and the slave DSP is not the same. 66 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 67 If this is not the case, contact Technical an irreparable fault. 67 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 68 If this is not the case, contact Technical Support. The EEPROM is ID76 UnrecoverREADEEPROM unrecoverable. 68 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 69 The software of the The software version is Contact Technical Support to update ID94 control board and unsuitable the software. communication board 69 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 70: Maintenance

    Disconnect the AC and DC power to the inverter before performing any cleaning operations. 70 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 71: Uninstalling

    With your cooperation in the correct disposal of this product, you contribute to the reuse, recycling and recovery of the product, and to the protection of our environment. 71 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00...
  • Page 72: Technical Specifications

    9. Technical specifications TECHNICAL DATA 1100TL-V3 1600TL-V3 2200TL-V3 2700TL-V3 3000TL-V3 3300TL-V3 72 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 73: Monitoring Systems

    (a), or by unscrewing the cover (b), as shown in the figure. Figure 39 – Port for external Wi-Fi adapter 73 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 74: Configuration

    Wi-Fi network reaches the place where the inverter is installed. If the Wi-Fi signal is present at the location where the inverter is installed, the configuration procedure can begin. 74 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 75 Note: Disconnect from any Wi-Fi networks to which you are connected by removing automatic access. Figure 42 – Disabling automatic reconnection to a network 75 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 76 3) If you are using a second-generation Wi-Fi adapter, you will be prompted for a password to connect to the inverter's Wi-Fi network. Use the password found on the box or on the Wi-Fi adapter. 76 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00...
  • Page 77 Note: To ensure that the adapter is connected to the PC or smartphone during the configuration procedure, enable automatic reconnection of the AP_******* network. Figure 45 – Password entry prompt 77 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 78 In the box that appears, enter “admin” as both the Username and Password. Figure 47 – Screen for accessing the web server to configure the Wi-Fi adapter 78 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 79 Received Signal Strength Indicator (RSSI) is greater than 30%. If the network is not visible, press the Refresh button. 79 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 80 Also check that the box below is set to Enable. Then click “Next” and wait a few seconds for verification. 80 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 81 9) Click “Next” again without ticking any of the options relating to the system security. Figure 51 - Screen for setting the security options (3) 81 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 82 12) Manually close the web page with the Close key on the PC por remove it from the background of the telephone. 82 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 83: Verification

    AP_******* network is no longer present. The absence of the Wi-Fi network in the list will confirm the successful configuration of the Wi-Fi adapter. 83 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 84 Signal Quality > other than 0% iii. IP address > other than 0.0.0.0 b. Remote server information i. Remote server A > Connected 84 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 85 NET (left LED ): off COM (central LED): steady on READY (right LED): flashing on Figure 56 - Initial status of LEDs 85 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 86 The adapter has now returned to its initial state. At this point, the configuration procedure can be repeated again. The adapter can only be reset when the inverter is switched on. 86 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 87: Troubleshooting

    NET (left LED): steady on COM (central LED ): off READY (right LED): flashing on Figure 59 - Irregular communication status between inverter and Wi-Fi 87 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 88 • 2) Irregular communication with remote server NET (left LED ): off COM (central LED): on READY (right LED): flashing on 88 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 89 Check that the 3G/LTE connection is active on your smartphone. Go to the Settings menu of the the phone), operating system (the gear icon on the screen with a list of all the apps installed on 89 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 90 Go to the Settings menu > Personal Hotspot and turn on the Personal Hotspot option. The hotspot is now enabled. To change the password of the Wi-Fi network, select Wi-Fi password from the personal hotspot menu. 90 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 91 80 (direct from the network to external users). 91 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 92: Ethernet Adapter

    (a), or by unscrewing the cover (b), depending on the inverter model, as shown in the figure. Figure 64 – Port of the Ethernet adapter 92 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 93 4) Connect the Ethernet adapter to the appropriate port, making sure to follow the direction of the connection and ensure correct contact between the two parts. Figure 66 – Inserting and securing the ethernet adapter 93 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 94: Verification

    Status of LEDs present on the adapter 1) Initial status: NET (left LED ): off COM (central LED): steady on SER (right LED): flashing on 94 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 95 NET (left LED): steady on COM (central LED): steady on SER (right LED): flashing on Figure 69 - Final status of LEDs 95 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 96: Troubleshooting

    RJ45 connector is correctly crimped. Irregular communication with remote server NET (left LED ): off COM (central LED): on SER (right LED): flashing on 96 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 97: Adapter

    10.3. 4G adapter The ZCS 4G adapters are sold with a virtual SIM integrated into the device with data traffic fee included for10 years, which is adequate for the proper transmission of data to monitor the inverter. In order to monitor the inverter, the RS485 communication address must be set to 01 directly from the display.
  • Page 98: Installation

    (a), or by unscrewing the cover (b), depending on the inverter model, as shown in the figure. Figure 72 – Port of the 4G adapter 98 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 99 5) Unlike Wi-Fi cards, the 4G adapter does not need to be configured and starts transmitting data shortly after the inverter is switched on. 99 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 100: Verification

    NET (left LED): flashing on (off and on at equal intervals) COM (central LED): steady on SER (right LED): steady on 100 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 101 If the value is not 01, go to “Settings” (basic settings for hybrid inverters) and enter the Modbus Address menu where the 01 value can be set. 101 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 102 Check the status of the 4G adapter and that there are no external signs of wear or damage. 102 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev. 1.1 of 12/03/2021 - Application: GID...
  • Page 103: Warranty Terms And Conditions

    11. Warranty terms and conditions To view the Warranty Terms and Conditions” offered by ZCS Azzurro, please refer to the documentation inside the product box and on the website www.zcsazzurro.com. 103 / 103 User’s Manual 1PH 1100TL-3300TL-V3 Rev. 1.1 12/03/2021 Identification: MD-AL-GI-00 Rev.

This manual is also suitable for: