Door alarm
The "o16" function is activated during a coordinated defrost
Control problem
No refrigerant selected
Defrost stopped based on time instead of, as wanted, on temperature
Fault in controller
Defrost sensor disconnected
Short-circuited defrost sensor
Change battery and check clock
S4 (Sout) sensor disconnected
Short-circuited S4 (Sout) sensor
S3 (Sin) sensor disconnected
Short-circuited S3 (Sin) sensor
S2 sensor disconnected
Short-circuited S2 sensor
Pressure transmitter error
Operating status
The controller goes through some regulating situations where it is just waiting for the
next point of the regulation. To make these "why is nothing happening" situations vis-
ible, you can see an operating status on the display. (The operating status cannot be
seen, however, if there is an active A or E alarm).
The status number means the following:
Waiting for end of the coordinated defrost
When the compressor is operating it must run for at least x minutes.
When the compressor is stopped, it must remain stopped for at least x minutes.
The evaporator drips off and waits for the time to run out
Refrigeration stopped by the internal or external start/ stop
Thermostat is cut-out
Defrost sequence. Defrost in progress
Defrost sequence. The fan waits for the time to run out
Refrigeration stopped due to open ON input or stopped regulation
Door is open. DI input is open
Melt function in progress. Refrigeration is interrupted
Modulating thermostat control
Emergency cooling due to sensor error
Start-up phase 2. Evaporator being charged
Adaptive control
Start-up phase 1. Signal reliability from sensors is controlled
Manual control of outputs
No refrigerant selected
Delay on outputs during start-up
Password required. Set password
EKC 414A
Manual RS8CK502 © Danfoss 05-2005
A4
Door alarm
A5
Max Hold Time
A10
Inject. prob.
A11
No Rfg. sel.
-
Max Def. Time
E1
Contr. fault
E4
Sdef error
E5
Sdef error
E6
-
E7
Sout error
E8
Sout error
E9
Sin error
E10
Sin error
E15
S2 error
E16
S2 error
E20
P0 inp. error
(Measurement)
EKC state
(The operating status can be read in
the AKM programme, even if there is
an active A or E alarm).
S1
1
S2
2
S3
3
S4
4
S10
10
S11
11
S14
14
S15
15
S16
16
S17
17
S18
18
S19
19
S20
20
S22
22
S23
23
S24
24
S25
25
S26
26
non
0
PS
11