Danfoss EKC 414A Manual page 16

Controller for controlling one evaporator
Hide thumbs Also See for EKC 414A:
Table of Contents

Advertisement

Continued from previous page
Service
The following readouts can be performed via the belonging parameter
Defrost sensor S5 S
def
Status on DI-input
Defrost time
Air temperature S3 (S
)
in
Status on night operation (on or off )
Status on ON-input
Status on DO-output
Air temperature S4 (S
)
out
Thermostat temperature
Thermostat cut-in time
Temperature at S2
Superheat
Superheat reference
AKV valve's actual opening degree
Evaporating pressure
Evaporating temperature
Factory setting
If you need to return to the factory-set values, it can be done in this way:
- Cut out the supply voltage to the controller
- Keep both buttons depressed at the same time as you reconnect the supply voltage
16
Para-
meter
°C
u09
u10
min.
u11
u12
°C
u13
u14
u15
u16
°C
u17
°C
u18
min.
u20
°C
u21
K
u22
K
%
u23
u25
bar
°C
u26
Manual RS8CK502 © Danfoss 05-2005
The controller can give the following messages:
Error message
E1
Fault in controller
E4
Defrost sensor disconnected
E5
Shortcircuited defrost sensor
E6
Change battery and check clock
E7
S4 (S
E8
Shortcircuited S4 (S
E9
S3 (S
E10
Shortcircuited S3 (S
E15
S2 sensor disconnected
E16
Shortcircuited S2 sensor
E20
AKS 32R fault
Alarm message
A1
High temperature alarm
A2
Low temperature alarm
A4
Door alarm
Function "O16" activated during a coordinated
A5
defrost
A10
Control problem
A11
No refrigerant selected
Status message
S1
Waiting for end of the coordinated defrost
S2
Waiting for end of compressor ON time
S3
Waiting for end of compressor OFF time
Defrost sequence. Evaporator drips off and
S4
waits for the time to expire
Refrigeration stopped by the internal or exter-
S10
nal start/stop function
S11
Thermostat cut out
S14
Defrost sequence. Defrost in progress
S15
Defrost sequence. Fan waiting for time to elapse
S16
Refrigeration stopped due to open ON input
S17
Door is open. Input DI is open
Melt function in progress (refrigeration inter-
S18
rupted)
S19
Modulating thermostat control
S20
Emergency refrigeration due to sensor error
S22
Start-up phase 2. Evaporator is charged
S23
Adaptive control
Start-up phase 1. Signal reliability from the sen-
S24
sors is checked
S25
Manual control of outputs
S26
No refrigerant selected
non
Time delay on outputs during start-up
PS
Password required. Set password
) sensor disconnected
out
)
out
) sensor disconnected
in
) sensor
in