Tripp Lite SMART1524ET Owner's Manual page 42

Hide thumbs Also See for SMART1524ET:
Table of Contents

Advertisement

Available languages

Available languages

Operation
High Back / Buck Back - The High Back view-only value displayed is based on
the High Limit and High Gap settings. The Buck Back view-only value displayed is
based on the Boost High and High Gap settings. See HIGH GAP (#63) for more
information.
Low Back / Boost Back - The Low Back view-only value displayed is based on the
Low Limit and Low Gap settings. The Boost Back view-only value displayed is based
on the Boost High and Low Gap settings. See LOW GAP (#64) for more information.
*) High back [### Vac]
*) Low back [### Vac]
*) Boost back [### Vac]
*) Buck back [### Vac]
6. Programmable Contacts Setup - This option allows customization of the
notification configuration for the UPS six output dry contacts and one input contact.
[0-MAIN MENU]
[6-PROGRAMMABLE CONTACTS SETUP]
70) Contact C1 = [Disabled]
71) Contact C2 = [Disabled]
72) Contact C3 = [Disabled]
73) Contact C4 = [Disabled]
74) Contact C5 = [Disabled]
75) Contact C6 = [Disabled]
76) PROGRAM I/P Contact = [EXT FAN FAILED]
>
Programmable Contacts Sub-Menu Options
Contacts C1, C2, C3, C4, C5, C6 - Selecting any of these six output dry contacts
enables setting the appropriate notification type for each set of dry contacts. To
configure reporting configurations for contacts C1 through C6, navigate to each
contact individually and select the desired configuration from the list of seven
available options (default configuration: C1 - C6 = DISABLED).
[0-MAIN MENU]
[6-PROGRAMMABLE CONTACTS SETUP]
[70-CONTACT C1]
Current Setting is [Disabled]
0) Set to [On Battery]
1) Set to [Battery Low]
2) Set to [Timer Time Up]
3) Set to [Summary Alarm]
4) Set to [UPS Fault]
5) Set to [UPS Shutdown]
6) Set to [DISABLED]
>
42

Advertisement

Table of Contents
loading

This manual is also suitable for:

Smart1548etAg-88e6Ag-88e5

Table of Contents