Operation
• PASSWORD: Enables the selection of a new, user-selected 4-digit password. To
configure the UPS with a new password, navigate to the PASSWORD screen and
select the SELECTING PASSWORD on-screen option. The UPS will request a new
4-digit password be entered. Once entered, the UPS will display SETTING AGAIN
and request the same 4-digit password be entered again for confirmation.
Note: Factory default password is 1111; please keep track of the new password to enable
future settings and control changes.
4. CONTROL: There are two pages of UPS CONTROL settings that are available to
perform testing, display output power status and reset UPS events. Each of these
pages contain sub-menu UPS control options.
Note: PASSWORD REQUIRED. (Factory default password is 1111)
First CONTROL Screen (4 items)
• SELF TEST: Selecting the SELF TEST option will cause the UPS to switch to
battery mode for the duration selected in the SETTINGS/TEST TIME field (factory
default is one minute). The UPS must be in Normal, Boost or Buck mode before
a self-test will successfully initiate. To initiate a SELF TEST, navigate to the SELF
TEST screen and select the START option. Once entered, the UPS will switch to
battery mode to test the battery, inverter and battery transfer circuits for proper
operation. To interrupt a self-test, select the STOP option from the SELF-TEST
screen.
• DRY TEST: Selecting the DRY CONTACT TEST option will simultaneously test all
output dry contacts for 1 minute. To initiate a DRY CONTACT TEST, navigate to
the DRY TEST screen and select ON or OFF for the desired testing configuration.
Selection options include:
Select ON to energize all 6 dry contacts for 1 minute
Select OFF to de-energize all 6 dry contacts for 1 minute
Select CANCEL to cancel the test immediately
• EXT FAN TEST: Selecting the EXTERNAL FAN TEST option will test the external
fan for a period of 1 minute. To initiate an EXTERNAL FAN TEST, navigate to the
EXT FAN TEST screen and select ON or OFF for the desired testing configuration.
Selection options include:
Select ON to energize the external fan for a period of 1 minute
Select OFF to de-energize the external fan for a period of 1 minute
Select CANCEL to cancel the test immediately
• ON/OFF CONTROL: Selecting the UPS OUTPUT option enables the setting of
UPS output power to be OFF or ON in Inverter, Boost, Buck and Normal modes.
To turn UPS OUTPUT OFF or ON in these operating modes, navigate to the UPS
OUTPUT screen and select the ON or OFF setting.
Select ON to enable UPS output in Inverter, Boost, Buck and Normal modes
Select OFF to disable UPS output in Inverter, Boost, Buck and Normal modes