Operation
Sense Type (#57) - Selecting this option enables configuration of UPS AC power
sensing to maximize UPS operation for standard line power AC and generator
power applications. To configure, navigate to the SENSE TYPE screen and select
the desired input power configuration to the UPS or GENERATOR setting (default=
GENERATOR).
[0-MAIN MENU]
[5-LINE CONDITIONING SETUP]
[57-SENSE TYPE]
Current setting is [Generator]
1) Generator
2) UPS
>
Line Qualify Time (#58) - Selecting this option enables configuration of the
amount of time the UPS monitors line power quality for stability before switching
to LINE POWER MODE as AC power is restored. To configure, navigate to the
LINE QUALIFY screen and select the desired time duration from the sub-menu list
(default = 30).
[0-MAIN MENU]
[5-LINE CONDITIONING SETUP]
[58-Line Qualify Time]
Current setting is [## Seconds]
0) Set to 3 seconds
1) Set to 10 seconds
2) Set to 30 seconds
>
High Limit (#59) - Selecting this option enables setting the high UPS transfer
voltage from line-power mode to battery mode. To configure, navigate to the HIGH
LIMIT screen and enter the desired voltage value (default = 152V).
HIGH LIMIT [###]
>
Low Limit (#60) - Selecting this option enables setting the low UPS transfer
voltage from line-power mode to battery mode. To configure, navigate to the LOW
LIMIT screen and enter the desired voltage value (default = 88V).
LOW LIMIT [###]
>
Boost Low (#61) - Selecting this option enables setting the boost-mode activation
voltage for undervoltage (BOOST) correction. To configure, navigate to the BOOST
LOW screen and enter the desired activation voltage (default = 102V).
BOOST LOW [###]
>
Enter new value. [120->152]
Enter new value. [088->120]
Enter new value. [096->120]