Operation
Backup Timer (#48) - Selecting this option enables configuration of the
BACKUP TIMER. This is the amount of runtime the UPS supports in battery mode
before sending a configured dry contact notification. To configure, navigate to
the BACKUP TIMER screen and select the desired duration multiplier. Selection
options between 1 and 32 increments. One increment is equal to 0.25 hours for a
maximum of 8 hours (default = [08]* 0.25 hours = 2.0 hours).
[0-MAIN MENU]
[4-SYSTEM SETTING]
[48-Backup Timer]
Current setting is [08] (Unit=0.25Hour)
Enter new value
>
LCD Backlight Timer (#49) - Selecting this option enables adjustment of the LCD
BACKLIGHT. To configure, navigate to the LCD BACKLIGHT screen and select the
desired setting. Selection options are: 5 MIN. and ALWAYS (default = 5 MIN).
[0-MAIN MENU]
[4-SYSTEM SETTING]
[49-LCD BackLight Timer]
0) 5 min
1) Always
>
Set to Default UPS (#50) - Selecting this option enables factory default
configuration of the UPS. To configure, navigate to the DEFAULT UPS screen and
select the YES option.
[0-MAIN MENU]
[4-SYSTEM SETTING]
[50-Set to Default UPS]
0) No
1) Yes
>
Set Date (#51) - Selecting this option enables the setting of the UPS date. To
configure, navigate to the SET DATE screen and enter the new YEAR / MONTH /
DAY information.
[0-MAIN MENU]
[4-SYSTEM SETTING]
[51-Set Date]
Current Date is [YEAR-MONTH-DAY]
Enter new value [##-##-##]
>