Operation
• BATTERY CAPACITY: Enables configuration of external battery pack capacity. To
configure, navigate via LCD to the BAT CAP setting screen and select the desired
capacity.
7Ah
9Ah (default value)
10Ah
12Ah
17Ah
26Ah
40Ah
65Ah
100Ah
• BATTERY COEFFICIENT: Enables adjustment of battery coefficient as battery
system ages to provide a better estimation of runtime remaining. To configure,
navigate to the Bat Coef screen and enter a coefficient setting from 0.5-2.0
(default value = 1.0).
Fourth SETTINGS Screen (4 selections)
• BAT GROUP: Enables adjustment to the size of external battery system capacity
by groups. If you are using a 200Ah battery system (2x 100Ah batteries), you
would set battery group to 2. To configure, navigate to the Bat Group screen and
enter the desired configuration. Settings range from 01-10 (01 is default value).
• BACKUP TIMER: Enables configuration of the BACKUP TIMER. This is the
amount of runtime the UPS supports in battery mode before sending a
configured dry contact notification. To configure, navigate to the BACKUP TIMER
screen and select the desired duration. Selection options are between 0 and
480 minutes, in increments of 15 minutes (default = 120 min.).
• DEFAULT UPS: Returns the UPS back to the factory default configuration. To
configure, navigate to the DEFAULT UPS screen and select the YES option.
• DEFAULT SNMP: Reserved for future use.
Fifth SETTINGS Screen (4 selections)
• BACKLIGHT TIMER: Selecting this option enables adjustment the amount of
time the LCD BACKLIGHT will stay on. To configure, navigate to the BACKLIGHT
screen and select the desired setting. Selection options are: 5 MIN. and ALWAYS
(default = 5 MIN).
• TEST TIMER: Enables the configuration of the UPS TEST TIME, the maximum
duration that the UPS will perform a battery mode self-test. To configure,
navigate to the TEST TIME screen and enter the desired maximum test time
duration from 1 to 255 minutes (factory default is 1 minute).
• SET DATE TIME: Enables the configuration of the UPS YEAR, DATE and TIME. To
configure, navigate to the SET DATE TIME screen and enter the year, date and
current time.