COMPONENT IDENTIFICATION

FRONT VIEW
RUN LED
ERR LED
■ STATUS INDICATOR LED
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator: Green LED turns on in normal operating
conditions.
SIDE VIEW
1
11
2
12
3
13
4
14
5
15
6
16
7
17
8
18
9
19
10
20
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
SW3
4
3
Unused
2
1
Start
Count
ON
■ SIDE DIP SW
(*) Factory setting
• Input Range: SW1-1 through 1-3, SW2-1 through 2-3
INPUT 1 (SW1)
INPUT 2 (SW2)
1
2
3
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
ON
OFF
ON
ON
• Count Mode: SW1-4, 1-5, SW2-4, 2-5
INPUT 1 (SW1)
INPUT 2 (SW2)
4
5
OFF
OFF
ON
OFF
OFF
ON
ON
ON
• Alarm Contact Form: SW1-6, 1-7, SW2-6, 2-7
INPUT 1 (SW1)
INPUT 2 (SW2)
ALARM 1
ALARM 2
6
7
OFF
OFF
ON
OFF
• Start Count: SW3-1
START COUNT AT POWER ON
SW
0*
1
count (*)
SW3-1
OFF
*1. Start (Reset) count can be modified using the R3CON PC
Configurator software.
Note: Be sure to set unused SW1-8, SW2-8 and SW3-2 through
3-4 to OFF.
R3-PA2
SW2
SW1
8
8
Unused
7
7
Alarm 2
6
6
Alarm 1
5
5
Count
4
4
Mode
3
3
Input
2
2
Range
1
1
ON
ON
INPUT RANGE
0 – 100 kHz (*)
0 – 10 kHz
0 – 1 kHz
0 – 100 Hz
0 – 10 Hz
0 – 1 Hz
0 – 0.1 Hz
COUNT MODE
Mode 0 : 1 count / pulse (*)
Mode 1 : 1 count / pulse
Mode 2 : 2 counts / pulse
Mode 3 : 4 counts / pulse
ALARM CONTACT FORM
ON (short) at alarm (*)
OFF (open) at alarm
Stored count
ON
EM-8386 Rev.4 P. 2 / 5