Flame presence check
Check the level of the flame detection signal with the "Check
mode" function from the flame control: the LEDs from 2 to 6
indicate the flame signal level, respectively. See "LED indicator
and special function" on page 33.
Check Mode
With burner flame on:
 hold the reset button on the flame control pressed for at
least 3 sec.;
 the button colour will change from green to yellow;
 each operating status signalling LED will be compared to
20% of the maximum brightness;
 press the reset button again (<0.5sec) to reset the standard
operation of the signalling LEDs.Boiler
Clean the boiler as indicated in its accompanying instructions in
order to maintain all the original combustion characteristics in-
tact, especially the flue gas temperature and combustion cham-
ber pressure.
Boiler
Clean the boiler as indicated in its accompanying instructions in
order to maintain all the original combustion characteristics in-
tact, especially the flue gas temperature and combustion cham-
ber pressure.
Gas leaks
Make sure that there are no gas leaks on the pipes between the
gas meter and the burner.
Gas filter
Replace the gas filter when it is dirty.
Combustion
If the combustion values found at the start of the intervention do
not satisfy current standards or anyway indicate a poor state of
combustion (consult the table below), contact the Technical As-
sistance Service for the necessary adjustments.
EN 676
Max. output
Theoretical
max. CO
GAS
2
0 % O
2
G 20
11.7
G 25
11.5
G 30
14.0
G 31
13.7
Air excess
Max. output
  1.2
  1.3
CO
% Calibration
2
mg/kWh
 = 1.3
 = 1.2
9.7
9
9.5
8.8
11.6
10.7
11.4
10.5
Maintenance
7.2.4

Safety components

The safety components should be replaced at the end of their life
cycle indicated in the following table.
WARNING
Safety component
Flame control
Flame sensor
Gas valves (solenoid)
Pressure switches
Pressure adjuster
Servomotor
(electronic cam) (if present)
Oil valve (solenoid)
(if present)
Oil regulator (if present)
Oil pipes/ couplings
(metallic)(if present)
Flexible hoses (if present)
Fan impeller
CO
 1000
 1000
 1000
 1000
Tab. M
31
GB
The specified life cycles do not refer to the warran-
ty terms indicated in the delivery or payment con-
ditions.
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
5 years or 30,000
pressurised cycles
10 years or 500,000 start-ups
Life cycle
15 years
10 years
Tab. N
20145860

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rs 1200/m bluRs blu series1133 t1134 t

Table of Contents