Firing Rates; Test Boiler - Riello RS 1000/M BLU Manual

Forced draught gas burners
Table of Contents

Advertisement

4.7

Firing rates

The MAXIMUM OUTPUT is chosen from within the continuous
diagram area (Fig. 2).
The MINIMUM OUTPUT must not be lower than the minimum
limit of the diagram:
RS 1000/M BLU = 4000 kW
RS 1200/M BLU = 5500 kW
26
24
22
20
18
16
14
12
10
8
6
4
2
0
1000 1800 2600 3400 4200 5000 5800 6600 7400 8200 9000
4.8

Test boiler

The burner/boiler combination does not pose any problems if the
boiler is EC approved and its combustion chamber dimensions
are similar to those indicated in the diagram (Fig. 3).
If the burner must be combined with a boiler that has not been EC
approved and/or its combustion chamber dimensions are clearly
smaller than those indicated in the diagram, consult the manufac-
turer.
The firing rates were obtained in special test boilers, according to
EN 676 regulations.
20145860
Technical description of the burner
RS 1000/M BLU
WARNING
RS 1200/M BLU
Thermal power – kW
In Fig. 3 you can see the diameter and length of the test combus-
tion chamber.
Example:
Output 7000 kW - diameter 120 cm - length 6 m.
MODULATING RATIO
The modulating ratio, obtained in test boilers in accordance with
standard EN 676, is 2.5:1.
10
GB
The firing rate value (Fig. 2) has been obtained
considering an ambient temperature of 20 °C, an
atmospheric pressure of 1013 mbar (approx. 0 m
a.s.l.), and with the combustion head adjusted as
shown on page 18.
D11991
9800
11400 12200
10600
D2448
Fig. 2
Fig. 3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rs 1200/m bluRs blu series1133 t1134 t

Table of Contents