MANUAL MODE

In this mode operation, Zone Fire and Fault alarms are still in operation, and first & second
stage sounders will operate, but the bottle output to the extinguishing agent will not operate.

RESET

To reset panel from a first stage alarm condition, activate the controls and press START/STOP
SOUNDERS, followed by SILENCE BUZZER, then RESET.
If the panel enters the second stage alarm (while in automatic mode), the panel cannot be
reset until the bottle output has operated, and the reset inhibit timer has ended.
The panel can NOT be reset from a fault condition. All faults are non latching, so when a
fault clears from the panel it will be automatically cleared from the display.
In the event of an alarm in the peripheral fire zones & crossed extinguishing zones
simultaneously, the reset button can be used to reset the peripheral zones, but won`t have an
effect on the extinguishing zones until the reset inhibit timer has ended.

FAULTS

When a fault is detected the relevant LED will illuminate and the buzzer will sound. The LCD will
display details of the fault(s) and show each detected fault in turn. Enable the controls and press the
Silence Buzzer button to silence the panel.
Press the NEXT and PREV buttons to manually cycle through the list of faults, the display will show
the number of faults in the lower right corner.
*** DEVICE FAULT ***
BOTTLE OUTPUT O/C
01/03