Omron CJ Series Operation Manual page 295

Master unit
Hide thumbs Also See for CJ Series:
Table of Contents

Advertisement

Bit
05
Module 5 Diagnostics
06
Module 6 Diagnostics
07
Module 7 Diagnostics
Consecutive bytes contain the diagnostics flags for Module 8 through 15, 16 through 23, etc.
The Module related diagnostics information is usually followed by the Channel related diagnostics,
which contain the actual diagnostics data per module.
 Channel Related Diagnostics
Channel related diagnostics contain diagnostics information related to a specific channel in a config-
ured I/O module, e.g. over peak current detected on current input channel 2, module 0.
The Channel related diagnostics information entry in the diagnostics message, always consists of
three bytes, which are outlined below. From these bytes the actual event can be deducted.
Module Identifier byte
Channel Identifier byte
Error Identifier byte
 Module Identifier Byte
Bit
00 to 05
Module number
06 to 07
Reserved
CJ-series PROFIBUS Master Unit Operation Manual for NJ-series CPU Unit (W509)
Name
When set, this bit indicates that there is Diagnostics information pending related
to configuration module 5.
When set, this bit indicates that there is Diagnostics information pending related
to configuration module 6.
When set, this bit indicates that there is Diagnostics information pending related
to configuration module 7.
7 6 5 4 3 2 1 0
1 0
7 6 5 4 3 2 1 0
7 6 5 4 3 2 1 0
Name
These bits contain the number of the configuration module, to which the channel,
reporting diagnostics belongs. The module number ranges from 0 to 63.
Fixed to 10.
The combination of bit 6 and 7 indicate the type of diagnostics, i.e. 10 indicates
Channel related diagnostics data.
Appendices
Description
Module number
Channel number
I/O type
Error type number
Channel size type
Description
A-29