 Adding/Inserting I/O Modules
To select the I/O modules, perform one of the following procedures.
• Select the I/O module that needs to be added in the Available Modules list, and double-click it
with the left mouse button. If more than one module must be added, repeat this step for the
other modules.
• Select the I/O module that needs to be added in the Available Modules list, and press either
the Insert or Append button. This method allows selection of more than one module, by
pressing either the Shift or the Ctrl key on the keyboard, while selecting the modules.
Note 1 When pressing the Insert button, the selected I/O module will be inserted above the
selected module in the Configured Modules list.
2 The selected I/O modules are sent to the slave device, in the same sequence as selected
in the user interface. Depending on the device, the sequence may be checked by the slave
device. If an incorrect sequence is sent, the I/O configuration is rejected. This is for exam-
ple the case with the OMRON PRT1-COM Multiple I/O PROFIBUS DP Interface.
3 A mandatory I/O module sequence is sometimes indicated in the GSD file, by using non-
PROFIBUS standard GSD file keywords (i.e. only interpreted by a specific configurator).
The Generic Slave DTM does not check such keywords. In this case, refer to the manual of
the specific device for details.
4 Also in this window are the maximum values, which can be set, and the totals of I/O data
that actually have been set. If, while selecting I/O modules one of the maximum values is
exceeded, a warning message will be displayed.
For the CJ1W-PRT21, the first four I/O modules have been selected. See figure below.
 Removing I/O Modules
To remove I/O modules from the Configured Modules list, perform one of the following procedures.
• Select the I/O module that needs to be removed from the Configured Modules list, and dou-
ble-click it with the left mouse button. If more than one module must be added, repeat this
step for the other modules.
CJ-series PROFIBUS Master Unit Operation Manual for NJ-series CPU Unit (W509)
5 Operation
5
5-13