Event code
Event name
38110000 hex
Double Mas-
ter Address
Error
38120000 hex
Parameter
Error
58010000 hex
Mode Com-
mand Error
88040000 hex
Disturbed
Bus Error
88050000 hex
PROFIBUS
Protocol
Error
88060000 hex
Hardware
Error
CJ-series PROFIBUS Master Unit Operation Manual for NJ-series CPU Unit (W509)
Meaning
There is a Master
• A second Master with the same address
address duplica-
has been detected on the Bus.
tion setting.
There is a problem
• An error has been detected in the con-
with the contents of
tents of the Parameter set while configur-
the parameters.
ing the PROFIBUS interface.
There is a problem
• More than one command mode switch
with the Mode set-
has been set.
ting of the Unit.
• A mode command switch is set while the
previous command is in progress.
• A mode transition command is given and
the Unit has detected that it does not
(yet) have a valid configuration or it
detected an internal error, either of which
prevented it from reaching that mode,
e.g. Invalid Parameter set and transition
to OPERATE mode.
Distorted messages
• The network is not properly terminated.
may have been
• A cable has been used which is too long
received by the
for the selected baud rate.
Unit.
A PROFIBUS pro-
• Network wiring.
tocol error has
• Other faulty devices on the Network.
occurred and
tokens have been
lost.
An error has
• Faulty wiring, broken message, short cir-
occurred on the
cuits, faulty bus timings or an active
bus.
device has been detected beyond the
Highest Station Address setting (HSA).
7 Troubleshooting and Maintenance
Assumed cause
Level
Maj
Prt
Min
Obs Info
X
X
X
X
X
X
7
7-27