Meter Specifications; Environmental Conditions; Electromagnetic Compatibility - red lion CUB5R Manual

Miniature electronic 8-digit dual counter and rate indicator
Hide thumbs Also See for CUB5R:
Table of Contents

Advertisement

O
RDERING
TYPE
CUB5
Optional Plug-in Cards
Accessories
*Crimson 2 software is available for download from http://www.redlion.net/
G
M
ENERAL
1.
DISPLAY: 8 digit LCD 0.46" (11.7 mm) high digits
CUB5R000: Reflective LCD with full viewing angle
CUB5B000: Transmissive LCD with selectable red or green LED backlight,
viewing angle optimized. Display color change capability with output state
when using an output module.
2. POWER: Input voltage range is +9 to +28 VDC with short circuit and input
polarity protection. Must use an RLC model MLPS1 or a Class 2 or SELV
rated power supply.
MODEL
DISPLAY COLOR
NO.
CUB5R000
---
CUB5B000
Red (max intensity)
CUB5B000
Green (max intensity)
3. COUNTER DISPLAYS:
Counter A: 8-digits, enabled in all count modes
Display Range: -9999999 to 99999999
Overflow Indication: Display flashes "
Counter B: 7-digits, enabled in Dual Counter Mode or batch counting
Display Designator: "
" to the left side of the display
b
Display Range: 0 to 9999999 (positive count only)
Overflow Indication: Display flashes "
Maximum Count Rates: 50% duty cycle
Without setpoint option card: 20 KHz (all count modes)
With setpoint option card: 20 KHz for any count mode except Dual Counter
(16 KHz), Quadrature x2 (14 KHz) and Quadrature x4 (13 KHz).
4. RATE DISPLAY: 6-digits, may be enabled or disabled in any count mode
Display Designator: "
" to the left side of the display
R
Display Range: 0 to 999999
Over Range Display: "
R OLOLOL
Maximum Frequency: 20 KHz
Minimum Frequency: 0.01 Hz
Accuracy: ±0.01%
5. COUNT/RATE SIGNAL INPUTS (INP A and INP B):
Input A: DIP switch selectable to accept pulses from a variety of sources.
See Section 2.0 Setting the DIP Switches for Input A specifications.
Input B: Logic signals only
Trigger levels: V
= 1.0 V max; V
IL
Current sinking: Internal 10KΩ pull-up resistor to +9 to 28 VDC
Filter (LO Freq.): Damping capacitor provided for switch contact bounce.
Limits input frequency to 50 Hz and input pulse widths to 10 msec min.
6. USER INPUT (USR): Programmable input. Connect to input common (INP
COMM) to activate function. Internal 10KΩ pull-up resistor to +9 to 28 VDC.
Threshold Levels: V
= 1.0 V max; V
IL
Response Time: 5 msec typ.; 50 msec debounce (activation and release)
2
7. MEMORY: Nonvolatile E
PROM memory retains all programming
parameters and count values when power is removed.
8. CONNECTIONS: Wire clamping screw terminals
Wire Strip Length: 0.3" (7.5 mm)
Wire Gage: 30-14 AWG copper wire
Torque: 5 inch-lbs (0.565 N-m) max.
9. CONSTRUCTION: This unit is rated for NEMA 4X/IP65 requirements for
indoor use. Installation Category I, Pollution Degree 2. High impact plastic
case with clear viewing window. Panel gasket and mounting clip included.

10. ENVIRONMENTAL CONDITIONS:

Operating Temperature Range for CUB5R000: -35 to 75°C
I
NFORMATION
MODEL NO.
DESCRIPTION
CUB5R
Dual Counter & Rate Indicator with Reflective Display
CUB5B
Dual Counter & Rate Indicator with Backlight Display
CUB5RLY
Single Relay Option Card
CUB5SNK
Dual Sinking Open Collector Output card
RS485 Serial Communications Card
CUB5COM
RS232 Serial Communications Card
MLPS1
Micro-Line Power Supply, 85 to 250 VAC
CBLPRO
Programming Cable RS232 (RJ11-DB9)
CBPRO
Programming Cable RS485 (RJ11-DB9)
SFCRD
Crimson 2 PC Configuration Software for Windows 98, ME, 2000, XP
S
ETER
PECIFICATIONS
INPUT CURRENT
INPUT CURRENT
@ 9 VDC WITHOUT
@ 9 VDC WITH
CUB5RLY0
CUB5RLY0
10 mA
30 mA
85 mA
115 mA
95 mA
125 mA
"
Cnt OVEr
"
bCntOVEr
"
= 2.4 V min; V
= 28 VDC
IH
MAX
= 2.4 V min; V
= 28 VDC
IH
MAX
Operating Temperature Range for CUB5B000 depends on display color
and intensity level as per below:
Red Display
Green Display
Storage Temperature: -35 to 85°C
Operating and Storage Humidity: 0 to 85% max. relative humidity (non-
condensing)
Vibration According to IEC 68-2-6: Operational 5 to 500 Hz, in X, Y, Z
direction for 1.5 hours, 5 g's.
Shock According to IEC 68-2-27: Operational 40 g, 11 msec in 3 directions.
Altitude: Up to 2000 meters
11. CERTIFICATIONS AND COMPLIANCES:
SAFETY
UL Recognized Component, File #E179259, UL61010A-1, CSA 22.2 No. 61010-1
Recognized to U.S. and Canadian requirements under the Component
Recognition Program of Underwriters Laboratories, Inc.
UL Listed, File # E137808, UL508, CSA C22.2 No. 14-M95
LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards
Type 4X Indoor Enclosure rating (Face only), UL50
IECEE CB Scheme Test Certificate #US/9257C/UL
CB Scheme Test Report #E179259-V01-S02
Issued by Underwriters Laboratories, Inc.
IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment
for measurement, control, and laboratory use, Part 1.
IP65 Enclosure rating (Face only), IEC 529

ELECTROMAGNETIC COMPATIBILITY

Emissions and Immunity to EN 61326: Electrical Equipment for
Measurement, Control and Laboratory use.
Immunity to Industrial Locations:
Electrostatic discharge
Electromagnetic RF fields
Fast transients (burst)
Surge
RF conducted interference
Power frequency magnetic fields
Emissions:
Emissions
Notes:
1. Criterion A: Normal operation within specified limits.
Refer to EMC Installation Guidelines for additional information.
12. WEIGHT: 3.2 oz (100 g)
2
PART NUMBER
CUB5R000
CUB5B000
CUB5RLY0
CUB5SNK0
CUB5COM1
CUB5COM2
MLPS1000
CBLPROG0
CBPRO007
*
SFCRD200
INTENSITY LEVEL
TEMPERATURE
1 & 2
-35 to 75°C
3
-35 to 70°C
4
-35 to 60°C
5
-35 to 50°C
1 & 2
-35 to 75°C
3
-35 to 65°C
4
-35 to 50°C
5
-35 to 35°C
EN 61000-4-2
Criterion A
4 kV contact discharge
8 kV air discharge
EN 61000-4-3
Criterion A
10 V/m
EN 61000-4-4
Criterion A
2 kV power
1 kV signal
EN 61000-4-5
Criterion A
1 kV L-L,
2 kV L&N-E power
EN 61000-4-6
Criterion A
3 V/rms
EN 61000-4-8
Criterion A
30 A/m
EN 55011
Class A

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cub5bCub5r000Cub5b000