Service Menus; Password Level; Set Points - Emerson Liebert.PEX+ Series User Manual

Precision air conditioner
Hide thumbs Also See for Liebert.PEX+ Series:
Table of Contents

Advertisement

34
Chapter 5 iCOM Controller

5.7 SERVICE MENUS

Press the right button at the first page of the USER MENUS, and you can enter the SERVICE MENUS, as shown in
Figure 5-9.
The SERVICE MENUS are displayed in five pages. Each page displays one or two submenus. Press the ENTER
button to highlight the submenus, and use the up or DOWN button to scroll up or down. Press the ENTER button to
enter the selected submenu.
SERVICE MENUS 1 / 5

PASSWORD LEVEL

C / F
%R
H
SE T
5.7.1 PASSWORD LEVEL
It is operated by Emerson service personnel.

5.7.2 SET POINTS

Different from the SET POINTS in the USER MENUS, the SET POINTS in SERVICE MENUS has many more
parameters. See Table 5-11 for the parameter descriptions.
Parameters
S102
TEMPSENS
S103
TEMP SET
S103
TEMP ACT
S104
CTRL TYPE
S106
TEMP PB
S106
TEMP INT
S107
TEMP DER
S108
AUTOSET
S109
TEMP DB
S110
SUPSENS
SUPPLY
S110
LIMIT SET
S111
HEAT DB
S113
COMP EN
S114
RCOMP SP
S115
RCOMP PB
S115
RET CO
S116
SUP CO
S118
CO F0
S118
CO F100
S119
TRANS CH
S120
CW F0
S120
CW F100
S121
BACK TSP
SERVICE MENUS
0 ?
??
?
SETPOINTS
WELLNESS
SERVICE MENUS
CALIERATION
NETWORK
NETWORK SETUP
Figure 5-9 SERVICE MENUS
Table 5-11 Descriptions of SET POINTS parameters
Default
Return Sensor
SUP,REM,RET
23.0 ° C
5.0-40.0 ° C
-
5.0-40.0 ° C
PI
PROP,PI,n.u.,INTEL
7K
2.2 -111.0 K
5.0min
0.0 - 15.0 min
0 sec
0-900 sec
Yes
Yes, No
1.1 K
0-20.0 K
No
No,Yes
5.0 ° C
5.0-27.0 ° C
0K
0-20.0 K
No
No,Ret,Sup,R+S
23.0 ° C
5.0-40.0 ° C
0.0K
0.0-10.0 K
0.0K
0.0-10.0 K
0.0K
0.0-10.0 K
0.60%/s
0.01 - 100.00 %/s
4.00%/s
0.01 - 100.00 %/s
4.00%/s
0.1 - 100.0 %/s
0.10 %/s
0.01-100.00%/s
0.60 %/s
0.01-100.00%/s
23.0 ° C
5.0-40.0 ° C
Liebert. PEX+Series Precision Air Conditioner
2 / 5
STANDBY
WELLNESS
4 / 5
SERVICE MENUS
SET
UP
OPTIONS SETUP
SERVICE INFO
Setting range
Temperature Control Sensor
Temperature set point
Temperature Control Type
Temperature proportional band set point, or the P in
PID control
Temperature integration time set point, or the I in PID
control
Temp Derivative Time
Autoset enable
Temperature Deadband
Supply Sensor
Supply Set point
Heaters deadband setting range
Enable Temp Compensation
Return Compensation Set point
Return Compensation Band
Return Compensation Value
Supply Compensation Value
DX Capacity Change at 0 %
DX Capacity Change at 100 %
Capacity Transition Filter
CW Capacity Change at 0 %
CW Capacity Change at 100 %
Backup Temperature Set point
User Manual
SERVICE MENUS
3 / 5
DIAGNOSTICS
SERVICE
SET
SET ALARMS
ALARMS
5 / 5
Description